V122

INSTALLATION GUIDE

WIRING COLOR CODES

CONTACT AND COIL SPECIFICATIONS

Resistive HOA Position Monitor

24VAC/DC

120VAC

LOW

wht/blue

COMM

wht/yellow

HI

wht/black

CONTACT OUTPUT

CONTROL SYSTEM INPUT

Common

HOA POSITIONS

WIRING EXAMPLE

Nipple mount directly to a panel

Nipple mount to a 2x or 4x electri-

cal box

To Load

To Controls

COIL

CONT

ACTS

To Load

To Controls

Wire
Nut

CO

IL

CONTACTS

HAND
OFF
AUTO

Up position: contacts are closed.

Middle position: contacts are open.

Down position: control system actuates the contacts.

PROGRAMMING THE RESISTIVE

MONITOR

The resistive monitor is a 0-10 kΩ analog output for monitoring the HOA switch
position. Please use the following ranges for the DDC scaling.

Condition

Range* (Ω)

Nominal Values without Wire

Resistance* (Ω)

Line Open

Greater than 8630

n/a

HOA Off

5290 to 8630

6190

HOA Auto

2880 to 5289

3391

HOA On

1200 to 2879

1406

Line Shorted

Less than 1200

n/a

* Ranges based on the presence of 0-1000 Ω of resistance due to wire. Average # of feet for 1000Ω
by wire AWG listed below.

Wire Type (AWG)

Distance Allowed (ft.)

26

12,189

22

30,864

18

78,296

† All 2-wire runs

Coil Voltage 24VAC/DC, 120VAC

Voltage

Coil Current

AC

DC

24V....................

75mA....................

32mA

120V....................

22mA

TYPICAL COIL PERFORMANCE

CONTACT RATINGS

Resistive..... 20A(r)@240VAC

8A@28VDC

14A@14VDC
Motor......... 250VAC, 1HP N.O. & N.C.