INSTALLATION GUIDE
WIRING COLOR CODES
CONTACT AND COIL SPECIFICATIONS
Resistive HOA Position Monitor
24VAC/DC
120VAC
LOW
wht/blue
COMM
wht/yellow
HI
wht/black
CONTACT OUTPUT
CONTROL SYSTEM INPUT
Common
HOA POSITIONS
WIRING EXAMPLE
Nipple mount directly to a panel
Nipple mount to a 2x or 4x electri-
cal box
To Load
To Controls
COIL
CONT
ACTS
To Load
To Controls
Wire
Nut
CO
IL
CONTACTS
HAND
OFF
AUTO
Up position: contacts are closed.
Middle position: contacts are open.
Down position: control system actuates the contacts.
PROGRAMMING THE RESISTIVE
MONITOR
The resistive monitor is a 0-10 kΩ analog output for monitoring the HOA switch
position. Please use the following ranges for the DDC scaling.
Condition
Range* (Ω)
Nominal Values without Wire
Resistance* (Ω)
Line Open
Greater than 8630
n/a
HOA Off
5290 to 8630
6190
HOA Auto
2880 to 5289
3391
HOA On
1200 to 2879
1406
Line Shorted
Less than 1200
n/a
* Ranges based on the presence of 0-1000 Ω of resistance due to wire. Average # of feet for 1000Ω
by wire AWG listed below.
Wire Type (AWG)
†
Distance Allowed (ft.)
26
12,189
22
30,864
18
78,296
† All 2-wire runs
Coil Voltage 24VAC/DC, 120VAC
Voltage
Coil Current
AC
DC
24V....................
75mA....................
32mA
120V....................
22mA
–
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive..... 20A(r)@240VAC
8A@28VDC
14A@14VDC
Motor......... 250VAC, 1HP N.O. & N.C.