Direct Current Sensors:
Split-Core, mA
and Voltage Output
DC Applications
Maximize Reliability
Minimize Installed Cost
SPECIFICATIONS
System Technology
H970: Open loop Hall effect; H971, EA20: Exclusive Pulse Reset Technology™
Amperage Range
H970: LC: 0-20/40/80; HC: 0-50/100/200 (slide switch selectable); H971: ±200ADC; EA20: 0-100ADC/0-150ADC/0-200ADC
Sensor Supply Voltage
H970: 15-30VAC/DC for 0-10VDC and 4-20mA outputs, 12-30VAC/DC for 0-5VDC output; H971, EA20: 12-24VDC*
Supply Current
35mA max.**
Insulation Class
H970: 840VDC; H971: 600VDC, EA20: 1000VDC
Temperature Range
H970: -15° to 60°C (5° to 140°F); H971, EA20: -30° to 60°C (-22° to 140°F)
Humidity Range
10-90% RH non-condensing
Output
H970: 4-20mA, 0-5VDC, 0-10VDC (2 options allowed per sensor); H971: Bidirectional 4-20mA (adjustable span)***; EA20: Unidirectional 4-20mA
Terminal Block Wire Size
24-14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
H970 Accuracy:
Accuracy
±3% F.S. (combined linearity, hysteresis, and repeatability)
Repeatability
±1%
Linearity
±1%
H971/EA20 Accuracy:
Accuracy at Ranges Below 100A
±0.5A (combined linearity, hysteresis, and repeatability)****
Accuracy at Ranges Above 100A
±0.5% full scale (combined linearity, hysteresis, and repeatability)****
Withstand Current 25,000ADC
Response Time
H970: 2 sec; H971, EA20: Less than 150 msec
Agency Approvals
UL 508 open device listing; CE: EN61010-1:2001-2, CAT III, pollution degree 2, basic insulation
Do not use the LED status indicators as evidence of applied voltage. For applications requiring double or reinforced insulation, please contact the factory.
* For currents over 120A, supply voltage must be at least 15V.
** For H971, at zero load current: 35mA max.; at 200A load current: 55mA to 100mA depending on supply voltage and current polarity.
*** Unless factory set per customer specifications (H971SP only).
**** For single conductor through product (no wraps).
pulse reset
technology™
U.S. Pat. #6,160,697; 6,522,517; 7,242,157
Year
Warranty
5
H971
FEATURES
All Models
●
Self-gripping iris for easy installation
●
Bracket can be installed in three different configurations...added flexibility
●
Status LED ensures proper wiring...easy set up
●
5-year warranty
H970 Multi-Output Model
●
Factory calibrated switch-selectable amp ranges (20/40/80 or 50/100/200) for
high resolution and installation ease
●
mA and DC voltage outputs...maximum installation flexibility
H971 Bidirectional Model
●
Patented Pulse Reset Technology™ significantly increases accuracy...sensor is
not affected by stray magnetic fields...minimize worry of magnetization from
over-current faults
●
User-adjustable span from ±20A to ±200A
●
Range can be factory-set per customer specifications (SP model)
EA20 Unidirectional Model
●
Patented Pulse Reset Technology™ significantly increases accuracy...sensor is
not affected by stray magnetic fields...minimize worry of magnetization from
over-current faults
●
100, 150, and 200A span versions available...application flexibility
DESCRIPTION
Hawkeye DC Sensors provide accurate load level monitoring of DC current loads. The
H970 combines a Hall Effect sensor with proven transducer circuitry. Slide-switch
selectable amperage ranges and field selectable mA and VDC outputs maximize
flexibility. The H971 uses Pulse Reset Technology™ with field proven circuitry to
provide a superior solution for DC applications with minimal risk of permanent
magnetization, ensuring longer life and better accuracy.
The H970 has low and high current options with slide switch selectable amperage
ranges and a choice of 0-5V, 0-10V, or 4-20mA outputs. The EA20 and the H971 have
4-20mA output only. The H971 also offers bidirectional sensing capability and a
user-adjustable span to allow greater application flexibility.
APPLICATIONS
●
Battery chargers
●
Motor armature current
●
Motor field current
●
Automotive loads
●
Marine equipment
●
Solar energy applications
●
Telecom
●
Electroplating
H970, H971, & EA20 SERIES