Veris Industries C SERIES Datasheet User Manual
Deluxe duct and wall co2 sensors, Individual or 3-in-1 co2, rh, and temperature, C series

AIR QU
ALIT
Y
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
DESCRIPTION
CDL/CWL carbon dioxide sensors maximize energy savings, while ensuring optimal
ventilation. These sensors allow ventilation systems to be controlled by the amount
of CO2 present in a space. The CWL/CDL Series detect fluctuations in CO2 levels and
signal ventilation systems to provide an inlet of fresh air optimal for the space at a
given time saving energy and ensuring tenant comfort.
APPLICATIONS
●
Controlling ventilation in response to occupancy
●
Facilitating compliance with ASHRAE 62.1 standard for air quality
●
Office buildings, conference rooms, schools, retail stores, etc.
Individual or 3-in-1 CO2,
RH, and Temperature
Deluxe Duct and Wall
CO2 Sensors
SPECIFICATIONS
Input Power
20 to 30VDC/24VAC; 100mA max.
Analog Output
4-20mA (clipped & capped)/0-5VDC/0-10VDC (selectable)
Operating Temperature Range
CDL: 0° to 50°C (32° to 122°F)
CWL: No humidity option: 0° to 50°C (32° to 122°F); With humidity option: 10° to 35°C (50° to 95°F)
Operating Humidity Range
0 to 95% RH noncondensing
Housing Material
High impact ABS plastic
CO2 Transmitter:
Sensor Type
Non-dispersive infrared (NDIR), diffusion sampling
Output Range
0-2000/5000 ppm (programmable)
Accuracy
±30 ppm ±2% of measured value*
Repeatability
±20 ppm ±1% of measured value
Response Time
<60 seconds for 90% step change
RH Transmitter:
HS Sensor
Fully replaceable, digitally profiled thin-film capacitive (32-bit mathematics) U.S. Patent 5,844,138
Accuracy
±2% from 10 to 80% RH @ 25°C; NIST traceable multi-point calibration
Hysteresis
1.5% typical
Stability
±1% @ 20°C (68°F) annually for two years
Output Range
0-100% RH
Temperature Coefficient
±0.1% RH/°C above or below 25°C (typical)
Temperature Transmitter:
Sensor Type
Solid-state, integrated circuit
Accuracy
±0.5°C (±1°F) typical
Resolution
0.1°C (0.2°F)
Output Range
10° to 35°C (50° to 95°F)
Relay Contacts:
1 Form C (SPDT) (on models without setpoint slider option)
1A@30VDC, resistive; 30W max.
RTD/Thermistors in wall packages are not compensated for internal heating of product.
EMC Conformance: Low voltage directive 2006/95/EC and EMC directive 2004/108/EC.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).
Note: Rough handling and transportation may cause a temporary reduction of CO
2
sensor accuracy. With time, the ABC function will tune the readings back to the correct accuracy range. The default tuning speed is limited to
30 ppm per week.
FEATURES
●
Microprocessor-based design increases accuracy and reduces installation time
●
Non-dispersive infrared technology (NDIR) repeatable to ±20 ppm ±1% of
measured value...high accuracy measurement
●
Innovative self-calibration algorithm...easy to maintain
●
5-year calibration interval (recommended)
●
Field-selectable outputs for operation flexibility
●
Integrated transducer and probe...eliminates the need to install a separate
pick-up tube
●
Snap-on faceplate...no screws required, making installation and service easy
●
Adjustable duct probe...simplifies installation and airflow monitoring
●
CO2, humidity, and temperature sensing all in one compact device...fewer units
to buy and install
C SERIES
CDL
CWL
HQ0001739.B 01131