Air qu alit y, Gmxa monitoring station, Application/wiring diagrams – Veris Industries G SERIES Datasheet User Manual
Page 2: Dimensional drawings, Accessories, Ordering information

AIR QU
ALIT
Y
800.354.8556
+1 503.598.4564
www.veris.com
Ventilation control for energy savings and OSHA compliance in
parking garages and service bays
GMxA Monitoring Station
The GMxA monitoring station accepts digital inputs from
up to four sensors to provide alarm status indication for
each channel, and a Form C (SPDT) fan actuation relay.
If any of the sensors detects CO levels above 25 ppm,
or if a fault is detected, the corresponding alarm status
indicator lights and the fan relay de-energizes (failsafe).
Typical Installation
Exhaust Fan
GM
Mount 5' above floor
To DDC system
(optional)
Supply Air Damper
APPLICATION/WIRING DIAGRAMS
GD/GW
GM
DIMENSIONAL DRAWINGS
Example:
G W V X S
ACCESSORIES
Verification Kits (AA32, AA39)
Replacement sensors (AA09)
Calibration gases (AA37, AA38)
Power Supplies: For a complete product offering check out our PS Series
G
D = Duct mount
W = Wall mount
Enclosure
Auxiliary Alarm
Output
US or EU
Output
A = Auxiliary Contact
X = None
= Standard
V = Field-selectable,
0-5/0-10VDC
M = 4-20mA
R = Relay only
Sensors = GWRXS
0 = Station Only
1 = Includes 1 Sensor
2 = Includes 2 Sensors
3 = Includes 3 Sensors
4 = Includes 4 Sensors
GM
Gas
Monitoring
Station
S
A
Example:
GM 4 A
GD/GW
GM
Sensor
Monitoring Station
ORDERING INFORMATION
Common
Out 0-5V/10V or 4-20mA
IN V+ 15-30VDC, 24VAC
N.O. Relay
N.O. Relay
OUTPUT
10V
5V
PPM
100
200
-
+
-
+
0-10V/0-5V
or
4-20mA
DDC
SYSTEM
15-30VDC
24VAC
CONTACTOR
POWER
FAN
POWER
N.C. CONTACTOR
SENSOR
N.C.
COMM
N.O.
Jumper
unused Inputs
as shown.
GMxA
MONITORING
STATION
V+
GND
IN
V+
IN
24VDC/VAC
COMMON
FAN
RELAY
CONTACTOR
POWER
FAN
POWER
N.C. CONTACTOR
Common
Out 0-5V/10V or 4-20mA
IN V+ 15-30VDC, 24VAC
N.O. Relay
N.O. Relay
OUTPUT
10V
5V
PPM
100
200
VERIS GD/GW SENSOR
(sold separately)
2.4"
(55 mm)
2.5"
(63 mm)
0.9" dia.
(22 mm)
4.5”
(114 mm)
4"
(102 mm)
5.0"
(127 mm)
2.25"
(57 mm)
2.8"
(71 mm)
4.9"
(125 mm)
0.5"
(13 mm)
6.5"
(166 mm)
GM CARBON MONOXIDE
MONITOR
ALARM STATUS
1
2
3
4
AA32
AA38
AA09
HQ0001743.B 01131