Typical coil performance contact ratings, Installation guide, Wiring color codes contact and coil specifications – Veris Industries V222 Install User Manual

Page 2: Hoa positions wiring example, Programming the resistive monitor

background image

Z203431-0B

PAGE 2

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

04122

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

V222

INsTallaTION GUIDe

Wiring Color CoDes

ContaCt anD Coil speCifiCations

Resistive HOA Position Monitor

208-277VAC

24VAC/DC

Common

Hoa positions

Wiring example

Nipple mount directly to a panel

Nipple mount to a 2x or 4x electri-

cal box

To Load

To Controls

COIL

CONT

ACTS

To Load

To Controls

Wire
Nut

CO

IL

CONTACTS

HAND
OFF
AUTO

Up position: contacts are closed.

Middle position: contacts are open.

Down position: control system actuates the contacts.

programming tHe resistive

monitor

The resistive monitor is a 0-10 kΩ analog output for monitoring the HOA switch
position. Please use the following ranges for the DDC scaling.

Condition

Range (Ω)*

Nominal Values without Wire

Resistance (Ω)*

Line Open

Greater than 8630

n/a

HOA Off

5290 to 8630

6190

HOA Auto

2880 to 5289

3391

HOA On

1200 to 2879

1406

Line Shorted

Less than 1200

n/a

* Ranges based on the presence of 0-1000Ω of resistance due to wire. Average # of feet for 1000Ω
by wire AWG listed below.

Wire Type (AWG)

Distance Allowed (ft.)

26

12,189

22

30,864

18

78,296

† All 2-wire runs

Coil Voltage 24VAC/DC, 208-277VAC

Voltage

Coil Current

AC

DC

24V....................

75mA

32mA

208V..................

36mA

277V..................

49mA

TYPICAL COIL PERFORMANCE

CONTACT RATINGS

Resistive..... 20A(r)@240VAC

8A@28VDC

14A@14VDC
Motor......... 250VAC, 1HP N.O. & N.C.