Installation guide, Network options – Veris Industries H8920-4 Install User Manual
Page 4
Z203509-0C
PAGE 4
©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
07111
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
H8920-4
INSTALLATION GUIDE
Indexing Option: Allows the node to access up to 63 H704 or H663 BCMs
for viewing and archiving purposes only
NETWORK OPTIONS
Bound Option: For all applications requiring binding*
H8920-4 LON Node
BCM
BCM
Modbus Network
LON Talk® Network
Lon Talk®
Controller
*If the bound option is employed, address each BCM at 1.
Node Identification
Wink: The LON Node will light its service LED for 5 seconds in response to a WINK
command.
Service Pin: A service pushbutton is provided for this method of identification.
(See Product Diagram section).
Neuron ID: The Neuron ID is located on a label on the back of the device. It can be
written down or peeled off as a removable sticker with bar code for easy insertion to
your network.
Program ID
The standard program ID for this product is 90:00:14:48:14:04:04:05
Up to 63 H704 or H663 Branch Current Monitors (BCM)
H8920-4 LON Node
LON Talk® Network
Modbus Network
Lon Talk®
Controller