Veris Industries Hx00 SERIES Datasheet User Manual
Current switches: fixed trip point, Hx00 series, Current monit oring

current monit
oring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
FEATURES
●
More reliable for status than relays across auxiliary contacts
●
Ideal for direct-drive units, unit vents, fan coil units, exhaust fans, and other
fixed loads
●
Great for lighting status–less expensive than 277V relays
●
Low 0.15 A turn-on (H300 and H600)...ideal for small exhaust fans (not intended
to detect belt loss)
●
Removable mounting bracket provides installation flexibility
●
Bracket on H900 can be installed in three different configurations...installer
convenience
●
Split-core H300, H600, and H900 for fast retrofit installation
●
Mini solid-core H800 and micro split-core H300 fit in tight enclosures...
saves valuable panel space
●
100% solid-state, no moving parts to fail
●
Polarity insensitive output
●
5-year warranty
Split-Core & Solid-Core On/Off
Status Current Switches
H300
H600
H800
H900
DESCRIPTION
Hawkeye x00 on/off current switches provide a cost-effective solution for
monitoring status on unit vents, exhaust fans, recirculation pumps, and other fixed
loads where belt loss is not a concern.
Veris has applied new technology to the H300, H600, and H800 models to achieve
impressive improvement in turn-on levels. The Hawkeye H300 and H600 now have
the lowest turn-on current in the industry at a mere 150mA!
APPLICATIONS
●
Monitoring status of electrical loads
●
Monitoring direct-drive units, exhaust fans, process motors, and other fixed
loads
●
Verifying lighting run times
Maximize Reliability
Minimize Installed Cost
SPECIFICATIONS
Sensor Power
N.O models: Induced from monitored current; H800NC: 5-30VDC, permanently connected
Insulation Class
600VAC RMS (UL), 300VAC RMS (CE)
Frequency Range
50/60 Hz
Temperature Range
H800, H800NC, H300, H900: -15° to 60°C (5° to 140°F)
H600: -15° to 40°C (5° to 104°F) (to 200A); -15° to 60°C (5° to 140°F) (to 150A)
H800HV: -40° to 50°C (-40° to 122°F) (to 200A); -40° to 75°C (-40° to 167°F) (to 100A, & 0.25A status output)
Humidity Range
10-90% RH non-condensing
Off State Leakage (H800NC Only)
34μA@5VDC, 200μA@30VDC
On State Voltage Drop (H800NC Only)
1.9VDC (max.) @0.1A
Terminal Block Wire Size
H600, H800, H900: 24-14 AWG (0.2 to 2.1 mm
2
); H300: 22-16 AWG (0.3 to 1.3 mm
2
)
Terminal Block Torque
H600, H800, H900: 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m); H300: 7 in-lbs (0.8 N-m)
Agency Approvals
UL 508 open device listing; CE: EN61010-1:2001-02, CAT III, pollution degree 2, basic insulation
Do not use the LED status indicators as evidence of applied voltage.
Current Switches:
Fixed Trip Point
US Patent No. 7,193,428
0.15 A
TURN-ON!
(select
models)
Year
Warranty
5
Hx00 SERIES
TM
HQ0001753.B 01131