Veris Industries H40 SERIES Datasheet User Manual
Field mount motor control device, H40 series, Current monit oring
current monit
oring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
DESCRIPTION
The Hawkeye 40 Series combines a switching relay, a current status sensor, and a
Hand-Off-Auto (HOA) switch into a single nipple-mounted housing. The low voltage
and line voltage wires are functionally separated from each other. A hinged lid on the
low voltage side allows easy relay connection and trip point adjustment, while the
high voltage side is closed for added safety. The H40 is connected in series between
the power source and the motor, and the relay and HOA switch control the on/off
functioning of the motor.
APPLICATIONS
●
Monitoring status and controlling small motor loads that are not driven by a
motor starter or contactor
• Exhaust fans
• Unit ventilators
• Fan terminal units
• Fan coil units
• Recirculating pumps
FEATURES
●
Separate high and low voltage sections...fast and economical installation by
low voltage electricians
●
Combines status sensor, command relay, and HOA switch in a single series
circuit...one line connection for three devices
●
Remote mounted enclosure eliminates the need to cram multiple devices into a
junction box
●
HOA provides true relay control...ideal for troubleshooting control wiring
●
SPST relay is field-selectable for N.O. or N.C. operation (some models)
●
5-year warranty
Line and Low Voltage
Separated Fractional Motor
Status with Command Relay
Field Mount Motor
Control Device
SPECIFICATIONS
Sensor Power (H40NE8A and H40ME8X only) Induced
Operating Temperature Range
-15°C to 50°C (5° to 122°F)
Operating Humidity Range
0-95% RH non-condensing
Frequency Range
50-60 Hz
Wire to Relay Contacts
H40 NE8A, H40NEXA, H40ME8X, H40MEXX: use 12 AWG (3.3 mm
2
) or larger wire
H40BAXA, H40AAXX: use 16 AWG (1.3 mm
2
) or larger wire
Low Voltage Terminal Block Wire Size
24-14 AWG (0.2 to 2.1 mm
2
)
Low Voltage Terminal Block Torque
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Relay:
Relay Contact Ratings
H40NE8A, H40NEXA: 16A@120/250VAC, 12A@277VAC, 1HP@120VAC, 8A@28VDC
H40ME8X, H40MEXX: SPDT 16A@120/277VAC, 1HP@120VAC, 2HP@277VAC, 16A@28VDC
H40BAXA: 10A@120/240/277VAC, 1/3HP@120VAC, 8A@28VDC
H40AAXX: SPDT 10A@120/240/277VAC, 1/3HP@120VAC, 10A@28VDC
Relay Coil Ratings
H40NE8A, H40ME8X, H40MEXX, H40NEXA: 24VDC 45mA nom.; 24VAC 78mA nom.; Class 2*
H40AAXX, H40BAXA: 10-30VAC@24-38mA; 10-30VDC@10-16mA; Class 2*
Agency Approvals
UL 508 open device listing
* In addition, coil input from other sources may be used as detailed in NEC 2008, Article 725.121.
Year
Warranty
5
H40
H40 SERIES
TM