Veris Industries Hx22 SERIES Datasheet User Manual
Current sensors: 0-5vdc analog output, Load trending with 0-5vdc output, Hx22 series
current monit
oring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
DESCRIPTION
The Hawkeye 722, 822, and 922 provide accurate load trending information with
a proportional 0-5VDC output signal. Slide-switches provide easy field selection of
monitored amperage range without jumpers (available on most models).
APPLICATIONS
●
Load trending
●
Motor control
●
Positive proof of flow
FEATURES
●
Self-powered analog current sensor simplifies installation
●
No external power required for sensor...eliminate power supplies
●
Self-gripping split-core for fast retrofit installation...no need to remove
conductor (H922)
●
Economical solid-core models feature adjustable bracket for easy alignment
●
No jumpers on unit...reduces installation error
●
Selectable factory calibrated ranges for increased flexibility and resolution
●
Some models available with three field-selectable ranges per unit...fewer
versions to choose from, stock, and install
●
Mini-sized H822 fits easily in tight enclosures
●
Removable bracket on H922 can be installed in three different configurations...
added flexibility
●
100% solid state, no moving parts to fail
●
5-year warranty
Load Trending With
0-5VDC Output
EXAMPLE LINEAR OUTPUT
Scale software as shown
SENSED AMPS
Selected Range*
0 VDC
0A
5 VDC
SENSOR OUTPUT
*Factory calibrated ranges selected
with the amperage range switch
SPECIFICATIONS
Sensor Power
Induced from monitored conductor
Insulation Class
600VAC RMS (UL), 300VAC RMS (CE)
Frequency
50/60 Hz nominal
Temperature Range
-15° to 60°C (5° to 140°F)
Humidity Range
10-90% RH non-condensing
Accuracy
±2% F.S. from 10% to 100% (selected range)
Response Time
2 sec.
Terminal Block Wire Size
24-14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals
UL 508 open device listing; CE: EN61010-1:2001-2, CAT III, pollution degree 2, basic insulation
For applications requiring double or reinforced insulation, please contact the factory
Current Sensors:
0-5VDC Analog Output
Year
Warranty
5
Maximize Reliability
Minimize Installed Cost
H922
H822
H722LC
Hx22 SERIES
TM
HQ0001764.B 01131