Rel ay s, Application/wiring examples, Wire color codes – Veris Industries V103 SERIES Datasheet User Manual
Page 2: Dimensional drawing, Ordering information, Contact output control system input

REL
AY
S
800.354.8556
+1 503.598.4564
www.veris.com
APPLICATION/WIRING EXAMPLES
Nipple mount directly to a panel
Nipple mount to any 2x or 4x electrical box
To Load
To Controls
Wire
Nut
CO
IL
CONTACTS
V102
RESISTIVE
INPUT
DO
WIRE COLOR CODES
Primary
Relay #2 for V101D/V201D only
Cable Faults:
OPEN = Infinite Ω
SHORT ~ 0Ω
Switch Positions:
HAND ~ 1.4kΩ
OFF ~ 6.2kΩ
AUTO ~ 3.4kΩ
GREY
GREY
BROWN
GREY
VIOLET
Switch Positions:
HAND = Brown wire closed to Common
OFF = Both wires open to Common
HAND
BROWN
GREY
VIOLET
OFF
BROWN
GREY
VIOLET
AUTO
AUTO = Grey wire closed to Common
VIOLET = Common
V102/202 Resistive HOA Position Monitor
V103/203 Digital HOA Position Monitor
MODEL RELAY
COIL
AMPERAGE RATING
HOA
HOA MONITOR
RELAY POWER LED
UL
V101
SPST, N.O.
10-30VAC/DC, 120VAC
10A
n
None
n
n
V101D
2x SPST, N.O.
10-30VAC/DC, 120VAC
n
None
n
n
V102
SPST, N.O.
10-30VAC/DC, 120VAC
n
Resistive
n
n
V103
SPST, N.O.
10-30VAC/DC, 120VAC
n
Digital
n
n
V201
SPST, N.O.
10-30VAC/DC, 208-277VAC
n
None
n
n
V201D
2x SPST, N.O.
10-30VAC/DC, 208-277VAC
n
None
n
n
V202
SPST, N.O.
10-30VAC/DC, 208-277VAC
n
Resistive
n
n
V203
SPST, N.O.
10-30VAC/DC, 208-277VAC
n
Digital
n
n
Some devices are plenum rated per UL 1995...see White Paper VWP01 at veris.com for details
DIMENSIONAL DRAWING
2.0"
(52 mm)
2.5"
(64 mm)
3/4" NPT Nipple
2.3"
(59 mm)
4.0"
(103 mm)
3.8"
(97 mm)
ORDERING INFORMATION
Auto
Off
Hand
HOA
Switch
BROWN
BROWN
Common
10-30VAC/DC
120VAC
White
HI (101D)
wht/red
LOW
grey/wht
COMM
wht/violet
208-277VAC
HI (201D)
wht/orange
CONTACT OUTPUT
CONTROL SYSTEM INPUT
red
red
viole
t
viole
t
oran
ge
oran
ge
whit
e
whit
e
or
*
White
Grey
White
10-30VAC/DC
208-277VAC
or
120VAC
HI
wht/brown
LOW
wht/blue
COMM
wht/yellow
HI
wht/black
White
brow
n
brow
n
CONTACT OUTPUT
CONTROL SYSTEM INPUT
Common
E150462
HQ0001838.B 01131