Veris Industries H923 SERIES Datasheet User Manual
Current sensors: 0-10vdc analog output, Load trending with 0-10vdc output, Current monit oring

current monit
oring
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
DESCRIPTION
The Hawkeye 723LC, 723HC, and H923 Series provide accurate load trending
information with a proportional 0-10VDC output signal. Devices offer three
amperage range options, with slide-switch selection for easy field adjustment –
no need for jumpers.
APPLICATIONS
●
Load trending
●
Motor control
●
Fan/pump status
FEATURES
●
Self-powered analog current sensor 0-10VDC output
●
Self-gripping split-core for fast retrofit installation...no need to remove
conductor (H923)
●
No jumpers on unit...reduces installation error
●
No external power required for sensor
●
Factory calibrated field-selectable ranges for high resolution and
installation ease
●
One device to stock and install...reduces installation charges
●
Removable mounting bracket for installation flexibility
●
Bracket on H923 can be installed in three different configurations...
added flexibility
●
100% solid state...no moving parts to fail
●
5-year warranty
Load Trending With 0-10VDC Output
SENSOR OUTPUT
Selected Range
0V
0A
10V
SENSED AMPS
EXAMPLE LINEAR OUTPUT
Scale software as shown
Maximize Reliability
Minimize Installed Cost
SPECIFICATIONS
Sensor Power
Induced from monitored current
Insulation Class
300VAC RMS
Frequency Range
50/60 Hz
Temperature Range
-15° to 60°C (5° to 140°F)
Humidity Range
10-90% RH, non-condensing
Accuracy
±2% F.S. from 10% to 100% (selected range)
Response Time
2 sec.
Terminal Block Wire Size
24-14 AWG (0.2 to 2.1 mm
2
)
Terminal Block Torque
3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Agency Approvals
UL 508 open device listing; CE: EN61010-1:2001-2, CAT III, pollution degree 2, basic insulation
For applications requiring double or reinforced insulation, please contact the factory
Current Sensors:
0-10VDC Analog Output
Year
Warranty
5
H723HC
H923
H723 SERIES & H923
TM
HQ0001765.B 01131