INSTALLATION GUIDE
H606
OPERATION
The H606 is a current-sensitive switching device that monitors current (amperage) in
the conductor passing through it. A change in the conductor’s amperage that crosses
the adjustable switch threshold plus the hysteresis value causes the resistance of
the FET status output to change state, similar to the action of a mechanical switch.
In this model, the setpoint is adjustable through the action of a twenty (20) turn
potentiometer (see the CALIBRATION section). The status output is suitable for
connection to building controllers or other appropriate data acquisition equipment
operating at 5 to 30 volts. The H606 requires 5 to 30 VDC external power supply to
generate its output.
TROUBLESHOOTING
Problem
Solution
No Reading at Controller
• Check sensor calibration (see above)
• Check for control voltage/current at sensor (<30V, <0.2A)
• Check for amperage in monitored conductor (> 1.25A)
• Check that at least 5 VDC are across the contacts.
• Assure that sensor core mating surfaces are clean and that
the core clamp is completely closed
Setpoint screw has no
stops
The setpoint screw has a slip-clutch at both ends of its travel to
avoid damage. Twenty turns CCW will reset the sensor to be
most sensitive. Repeat calibration above.
Both LEDs are lit
Setpoint screw is too far clockwise. See solution above.
4x
0.5A
VERIS INDUSTRIES
Portland, Oregon 97223
1-800-354-8
556
Hawkeye
®
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
H68xx‑5A CT
240A
300A:
5A
4A
VERIS INDUSTRIES
Portla
nd, Oregon
97223
1-800-354-
8556
Hawkeye
®
> 50A (Sensor max.)
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
CALIBRATION
A. To monitor under-current (belt loss, coupling shear, status)
A
OK!
!
B. To monitor over-current (mechanical problems, seized impeller)
A
OK!
!
OK!
STATUS
OK!
STATUS
Before beginning calibration, establish normal load conditions.
OK!
A
OK!
Then choose either A or B below.
< 1.25 A (Sensor Min.)
1. Turn setpoint screw
clockwise until Status Closed
LED turns on.
2. Slowly turn the screw counter-clockwise until the Status Open LED just
turns on.
3. Turn the
setpoint screw an
additional 1/4 turn
counter-clockwise
for operational
margin.
3. Turn the
setpoint screw
an additional 1/4
turn clockwise
for operational
margin.
1. Turn setpoint screw
counter-clockwise until Status
Open LED turns on.
2. Slowly turn the setpoint screw clockwise until the Status Closed LED
just turns on.
Setpoint
Status
Open
STOP
Setpoint
Status
Closed
STOP
1/4
Setpoint
+
Setpoint
Status
Closed
STOP
Setpoint
Status
Open
STOP
+
1/4
Setpoint
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) to add range for a low current load on a high
current source.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer.