Installation guide current monitoring h608, Caution – Veris Industries H608 Install User Manual
Page 3
Z201757-0H
Page 3 of 4
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 07131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Current Monitoring
H608
TM
Notes
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) current transformer (CT) as shown. This technique can be combined with wrapping (see below) to add
range for a low current load on a high current source.
DANGER: 5A CTs can present
hazardous voltages. Install
CTs in accordance with
manufacturer's instructions.
Terminate the CT secondary
before applying current.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
H68xx-5A CT
>175 A (sensor max.)
< 0.5 A (Sensor Min.)
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor body to produce multiple turns. This increases
the current measured by the transducer. Program the controller to account for the extra turns (e.g., if four turns pass through the
sensor (as shown) divide the normal reading by 4).
240A
300A:
5A
4A
4x
0.5A
0.3 A