Veris Industries PX SERIES Datasheet User Manual
Dry media differential pressure transducers, Px series, Pressure

PRESSURE
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
SPECIFICATIONS
Media Compatibility
Dry air or inert gas
Input Power
12-30VDC, or 24VAC nominal; 2-wire: 20mA max.; 3-wire: 30mA max.
Output
Field-selectable: 2-wire, loop-powered 4-20mA (DC only, clipped and capped), or 3-wire 0-5V/0-10V *
Pressure Ranges:
PX: 01
Unidirectional: 0.1/0.25/0.5/1.0” W.C. F.S., switch selectable
Bidirectional: ±0.1/±0.25/±0.5/±1.0” W.C. F.S., switch selectable
Unidirectional: 25 Pa/50 Pa/100 Pa/250 Pa, F.S., switch selectable
Bidirectional: ±25 Pa/±50 Pa/±100 Pa/±250 Pa, F.S., switch selectable
PX: 02
Unidirectional: 1.0/2.5/5.0/10” W.C. F.S., switch selectable
Bidirectional: ±1.0/±2.5/±5.0/±10” W.C. F.S.,switch selectable
Unidirectional: 0.250 kPa/0.500 kPa/1.000 kPa/2.500 kPa, F.S., switch selectable
Bidirectional: ±0.250 kPa/±0.500kPa/±1.000 kPa/±2.500 kPa, F.S., switch selectable
PXU: 05
Unidirectional: 0.1/0.25/0.5/1.0/2.5/5/10” W.C. 25 Pa/50 Pa/100 Pa/250 Pa/0.5 kPa/1 kPa/2.5 kPa F.S. switch selectable
Bidirectional: ±0.1/0.25/0.5/1.0/2.5/5/10” W.C. 25 Pa/50 Pa/100 Pa/250 Pa/0.5 kPa/1 kPa/2.5 kPa F.S. switch selectable
Response Time
Standard: T95 in 20 sec, Fast: T95 in 2 sec, switch selectable
Mode
Unidirectional or bidirectional, switch selectable
Display (option)
Signed 3-1/2 digit LCD, indicates pressure, overrange indicator
Proof Pressure
3 psid (20.6 kPa)
Burst Pressure
5 psid (34.5 kPa)
Accuracy
±1% F.S. of selected range (combined linearity and hysteresis)
Temperature Effect
1" (250 Pa) models: 0.05%/°C; 10" (2.5 kPa) models: 0.01%/°C; (Relative to 25°C) 0° to 50°C (32° to 122°F)
Zero Drift (1-year)
1" (250 Pa) models: 2.0% max.; 10" (2.5 kPa) models: 0.5% max.
Zero Adjust
Pushbutton auto-zero and digital input (2-pos terminal block)
Operating Environment
0°- 60°C (32° to 140°F); 0 to 90% RH noncondensing
Fittings
Brass barb; 0.24” (6.1 mm) o.d.
Physical
UL 94 V-O Fire Retardant ABS
EMC Conformance: Low voltage directive 2006/95/EC; EMC directive 2004/108/EC.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).
* Minimum input voltage for 4-20mA operation: 250 Ω loop = 13VDC; 500Ω loop = 19VDC
DESCRIPTION
The digital PX Series differential pressure transducers utilize highly accurate,
microprocessor profiled sensors and an advanced ceramic capacitive sensing
element. Designed to monitor duct and room pressure in commercial buildings, the
PX Series offers exceptional job-site flexibility. PXP and PXD models feature four
field-selectable ranges. The PXU features seven field-selectable ranges, allowing just
one model to cover applications for 0-0.1” to 0-10” W.C. The directional mode jumper
is used to configure the transducer in unidirectional or bidirectional mode for room
and building static pressure applications. All models feature a pushbutton and digital
input terminal to zero the output. The microprocessor is programmed to prevent
accidental zero adjustment during normal operation.
APPLICATIONS
●
Static pressure in duct or room applications
●
Variable air volume system control
●
Filter status monitoring
●
Clean rooms, hospitals, fume hoods, computer rooms, and other very low
differential pressure applications
FEATURES
●
Excellent tolerance to overpressure and vibration reduces field failures
●
High accuracy digital sensor maintains calibration and reduces callbacks
●
High reliability sensor technology for long-term maintenance-free operation
●
Selectable ranges and scales reduce setup time & number of models
to stock
●
Microprocessor-based design allows for digitally profiled sensor increasing
product accuracy and reliability
●
Circuit protection prevents damage due to incorrect wiring
●
Monitors positive and negative pressure for application versatility
●
Flexibility: standard and fast response modes
●
LCD is ideal for setting up, troubleshooting, and measuring
●
Ceramic capacitive sensing element...highly stable linear output, reducing
offset errors
Selectable Ranges, LCD Display,
And Automatic Zero For
Easy Operation
Dry Media Differential
Pressure Transducers
Year
Warranty
5
PXP
PXU
PX SERIES
HQ0001827.B 01131