Veris Industries EP2 SERIES Datasheet User Manual
Electropneumatic transducers, Ep series, Pressure

PRESSURE
VERIS INDUSTRIES
800.354.8556
+1 503.598.4564
www.veris.com
SPECIFICATIONS
Input Power
24VAC/DC nominal, 30VAC max.; 150mA max.
Control Input
4-20mA/0-5V/0-10VDC; jumper-selectable
Input Impedance
4-20mA, 250Ω; 0-5V/0-10VDC, 10 kΩ
Manual Override
Jumper-selectable mode, digital pushbutton adjust
Alarm Contact
100mA@30VAC/DC (Pressure loss, manual mode, jumper selectable)
Accuracy
1% FS; combined linearity, hysteresis, repeatability
Compensated Temperature Range
-4° to 65°C (25° to 140°F)
Temperature Coefficient
±0.05%/°C
Operating Environment
10-90% RH noncondensing
Air Capacity
523 in
3
/min @ 45 psi (8570 cm
3
/min @ 310.3 kPa); 333 in
3
/min @ 20 psi (5456 cm
3
/min @ 137.9 kPa)
Supply Pressure
45 psig max.
Control Range
0-20 psig or 3-15 psig, jumper-selectable
Pressure Differential
0.1 psig (supply to branch)
Pressure Indication
Electronic, 3-1/2 digit LCD
Minimum Tubing Length
15 feet*
Port Connection
1/8” i.d. poly tubing
Media Connection
Clean, dry air, or inert gas. Do not use with oxygen service
*For shorter tubing runs use AA45 Pneumatic Capacitor
EMC Conformance: Low voltage directive 2006/95/EC; EMC directive 2004/108/EC.
EMC Special Note: Connect this product to a DC distribution network or an AC/DC power
adaptor with proper surge protection (EN 61000-6-1:2007 specification requirements).
Electropneumatic Transducers
Year
Warranty
5
DESCRIPTION
The EP2 Series electropneumatic pressure transducer uses micro-controlled poppet
valve technology for highly accurate pressure sensing in multiple applications. The
poppet valves consume no air, eliminating unnecessary air losses in the system and
allowing for stable and reliable operation. The EP2 is comes installed on standard
SnapTrack, and an optional dust cover is available to protect from the environment.
An LCD display and LED indicators make it easy to read system status at a glance.
APPLICATIONS
●
Hospitals
●
Schools
●
Pneumatic dampers/actuators
FEATURES
●
Field-selectable 4-20mA/0-5V/0-10VDC input for application flexibility
●
Poppet valve technology for quiet operation
●
Manual override with set and hold feature...great for commissioning
those leaky systems
●
Multi-point calibration; 3-15 psi (5 point calibration) and 0-20 psi
(6 point calibration)
●
Pressure loss alarm provides a contact closure if the EP2 is unable to
achieve the desired output within a fixed length of time
●
Failsafe vent solenoids bleed branch pressure on power failure for added safety
●
Optional transparent plastic dust cover (AA43) protects units from dust
and tampering (required for CE)
Micro-Controlled With High-
Performance, Low-Power Coil
Poppet Valve Technology
EP Series transducers are sold as an open device.
Observe handling precautions for static sensitive
devices to avoid damage to the circuitry which
would not be covered under the factory warranty.
EP2
EP SERIES
HQ0001828.B 01131