pressure
800.354.8556
+1 503.598.4564
www.veris.com
JP8
JP7
JP6
JP3
JP2
JP1
ZERO
Analog Reverse/Normal
Port Swap/Normal
Bidirectional/Normal
Fast/Slow Surge Damping
5V/10V Output
mA/Volts Output
POWER
REMOTE ZERO
(Dry Contact)
DIGITAL CONTROL
Analog Input
0-5V/0-10V
or 4-20mA
Optional
Digital Output
POWER SOURCE
12 to 30 VDC/24 VAC
SIGNAL
COM
PW SERIES
/
Range
A
B
C
D
HI PORT
100 psi
100 psi
50 psi
50 psi
0 psi
LO PORT
0 psi
50 psi
50 psi
100 psi
100 psi
4-20mA
0-10V
+100 psi
+50 psi
0 psi
-50 psi
-100 psi
Bidirectional Operation
Input Conditions
Result
Outputs Read
DP
20mA
16mA
12mA
8mA
4mA
10V
7.5V
5V
2.5V
0V
17.0 bar
17.0 bar
8.5 bar
8.5 bar
0 bar
0 bar
8.5 bar
8.5 bar
17.0 bar
17.0 bar
+17.0 bar
+8.5 bar
0 bar
-8.5 bar
-17.0 bar
20mA
16mA
12mA
8mA
4mA
10V
7.5V
5V
2.5V
0V
Output is either
mA or V
e.g. PW-04
e.g. PW-08
Range (psi)
Model
PW-03
PW-04
PW-05
A
50
100
250
B
25
50
125
C
10
20
50
D
5
10
25
Range (bar)
A
3.5
7.0
17.0
B
1.75
3.5
8.5
C
0.7
1.4
3.4
D
0.35
0.7
1.7
e.g. PW-04
e.g. PW-08
Use the Range switch to
select F.S. differeintial
pressure.
Model
PW-06
PW-07
PW-08
Local Display
L = LCD Display
X = No Display
NIST
N = NIST
X = None
US or EU
S = Standard
3
C = CE
Operational Range
1
PW
1
Select operational range according to maximum gauge pressure, NOT differential pressure.
Example: High gauge pressure=90 psig, Select 100 psig model (04).
2
BARG models use BSPT threads on sensor fittings.
3
Not available with barg units
Example:
PW L X 04 C
ACCESSORIES
Bypass Valve assemblies (AA14A)
PW installed on bypass valve manifold (AA16A)
Snubbers (AA11, AA12), Steam siphon (AA13)
APPLICATION/WIRING DIAGRAM
DIMENSIONAL DRAWING
ORDERING INFORMATION
03 = 0-50 psig
04 = 0-100 psig
05 = 0-250 psig
06 = 0-3.5 barg
2
07 = 0-7.0 barg
2
08 = 0-17 barg
2
2.2"
(57 mm)
4"
(102 mm)
5.8"
(147 mm)
LOW
HIGH
WET DIFFERENTIAL PRESSURE
AA14A
AA13
AA11