Typical coil performance contact ratings, Installation guide, Wiring color codes contact and coil specifications – Veris Industries V421 Install User Manual
Page 2: Wiring example, Hoa positions, V421
![background image](/manuals/259722/2/background.png)
Z203429-0C
PAGE 2
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
05122
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
V421
INSTALLATION GUIDE
WIRING COLOR CODES
CONTACT AND COIL SPECIFICATIONS
Voltage
Coil Current
AC DC
24V.......................................... 120mA
64mA
277V........................................ 102mA
-
TYPICAL
COIL PERFORMANCE
CONTACT RATINGS
Resistive............................ 20A@240VAC
8A@28VDC
14A@14VDC
Motor.................................. 120VAC, 1HP
WIRING EXAMPLE
24VAC/DC
LOW
wht/blue
COMM
wht/yellow
CONTACT OUTPUT #1 N.O.
CONTACT OUTPUT #2 N.O.
CONTROL SYSTEM INPUT
Common
208-277VAC
HI
wht/brown
White
brow
n
brow
n
Nipple mount directly to a panel
Nipple mount to a 2x or 4x electrical box
* Isolate any unused wires, e.g. wire nut.
To Load A
To Controls
CONTROL
PANEL
COIL
To Load B
To Power
COM
N.O.
N.C.
To Load B
To Control
Wire
Nuts
CO
IL
CONTACTS
To Load A
To Power
N.C.
N.O.
COM
HOA POSITIONS
HAND
OFF
AUTO
Up position: contacts are closed.
Middle position: contacts are open.
Down position: control system actuates the contacts.
Relay 2 Relay 1