beautypg.com

Typical coil performance contact ratings, Installation guide, Wiring color codes contact and coil specifications – Veris Industries V421 Install User Manual

Page 2: Wiring example, Hoa positions, V421

background image

Z203429-0C

PAGE 2

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

05122

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

V421

INSTALLATION GUIDE

WIRING COLOR CODES

CONTACT AND COIL SPECIFICATIONS

Voltage

Coil Current

AC DC

24V.......................................... 120mA

64mA

277V........................................ 102mA

-

TYPICAL

COIL PERFORMANCE

CONTACT RATINGS

Resistive............................ 20A@240VAC

8A@28VDC

14A@14VDC

Motor.................................. 120VAC, 1HP

WIRING EXAMPLE

24VAC/DC

LOW

wht/blue

COMM

wht/yellow

CONTACT OUTPUT #1 N.O.

CONTACT OUTPUT #2 N.O.

CONTROL SYSTEM INPUT

Common

208-277VAC

HI

wht/brown

White

brow

n

brow

n

Nipple mount directly to a panel

Nipple mount to a 2x or 4x electrical box

* Isolate any unused wires, e.g. wire nut.

To Load A

To Controls

CONTROL

PANEL

COIL

To Load B

To Power

COM

N.O.

N.C.

To Load B

To Control

Wire
Nuts

CO

IL

CONTACTS

To Load A

To Power

N.C.

N.O.

COM

HOA POSITIONS

HAND
OFF
AUTO

Up position: contacts are closed.

Middle position: contacts are open.

Down position: control system actuates the contacts.

Relay 2 Relay 1