Installation guide, Typical coil performance contact ratings, Wiring example – Veris Industries V200 SERIES Install User Manual
Page 2: Wiring color codes contact and coil specifications, V200, Contact output control system input

Z202853-0B
PAGE 2
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
02122
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
V200
INSTALLATION GUIDE
N.C.
Common
10-30VAC/DC
LOW
wht/blue
COMM
wht/yellow
Common
N.O.
CONTACT OUTPUT
CONTROL SYSTEM INPUT
White
YELLOW
White
ORANGE
blue
blue
yello
w
yello
w
208-277VAC
HI
wht/brown
White
brow
n
brow
n
WIRING EXAMPLE
Nipple mount directly to a panel
Nipple mount to any 2x or 4x electrical box
To Load
To Controls
COIL
CONT
ACTS
To Load
To Controls
Wire
Nut
CO
IL
CONTACTS
WIRING COLOR CODES
CONTACT AND COIL SPECIFICATIONS
Pull in Voltage
AC
DC
10-30V..................................... 8
9
208-277V................................. 154
Drop Out Voltage
AC
DC
10-30V..................................... 2 3
208-277V................................. 36
Voltage
Coil Current
AC DC
10V.......................................... 25mA 14mA
12V.......................................... 25mA 14mA
24V.......................................... 31mA 16mA
30V.......................................... 39mA 18mA
208V........................................ 19mA
-
277V........................................ 25mA -
TYPICAL COIL PERFORMANCE
CONTACT RATINGS
Resistive.............. 10A@277VAC, 28VDC
Motor.................... 120VAC, 1/3HP N.O. & 1/6HP N.C.
240VAC, 1/3HP N.O. & 1/6HP N.C.
277VAC, 1/4HP N.O. & 1/8HP N.C.
Pilot Duty............. 277VAC, (1.7A), 480VA N.O.
Ballast.................. 277VAC, 1.7A
Tungsten............... 120VAC, TV3 N.O. TV2 N.C.
Gold Flash............. Yes