beautypg.com

Typical coil performance contact ratings, Installation guide, Hoa positions wiring example – Veris Industries V221 Install User Manual

Page 2: Wiring color codes contact and coil specifications

background image

Z203430-0B

PAGE 2

©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

04122

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

V221

INsTallaTION GUIDe

Hoa Positions

Wiring examPle

Nipple mount directly to a panel

Nipple mount to a 2x or 4x electrical box

To Load

To Controls

COIL

CONT

ACTS

To Load

To Controls

Wire
Nut

CO

IL

CONTACTS

Wiring Color CoDes

ContaCt anD Coil sPeCifiCations

208-277VAC

24VAC/DC

Common

HAND
OFF
AUTO

Up position: contacts are closed.

Middle position: contacts are open.

Down position: control system actuates the contacts.

Voltage

Coil Current

AC

DC

24V....................

75mA....................

32mA

208V....................

36mA

277V....................

49mA

Resistive..... 20A@240VAC

8A@28VDC

14A@14VDC
Motor......... 120VAC, 1HP N.O. & N.C.

TYPICAL COIL PERFORMANCE

CONTACT RATINGS

Coil Voltage 24VAC/DC, 208-277VAC