beautypg.com

Caution, Installation guide, Wiring diagram digital control – Veris Industries H970LCA Install User Manual

Page 2: Operation, Set-up and wiring, Scaling, Troubleshooting, Sensor output, H970lca, For load currents less than sensor minimum rating

background image

H970LCA

Z203252-0E

PAGE 2

©2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

10101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

INSTALLATION GUIDE

TM

opEration

The H970LCA is a current-sensitive device that monitors DC current (amperage)
in the conductor passing through it. The unit combines a Hall Effect sensor with
proven transducer circuitry, with a status output suitable for connection to building
controllers or other appropriate data acquisition equipment operating at up to
30 volts. The H970LCA requires supply voltage to generate its output. Selectable
amperage ranges and output types maximize the installation flexibility.

The H970LCA housing offers unprecedented mounting flexibility. The mounting
bracket can be attached in three different places. Additionally, the bracket is
compatible with the Veris AH01 DIN Rail clip, allowing DIN mounting.

notEs

For load currents less than sensor minimum rating:

Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the “window.” This increases the current measured
by the transducer.

Controller must be programmed to account for
the extra turns. e.g., if four turns pass through
the sensor (as shown) the normal controller
reading must be divided by 4.

CAUTION

RISK OF EQUIPMENT DAMAGE

• Derate the product’s maximum current for the number of turns

through the sensing window using the following formula.

Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor

• Failure to follow these instructions can result in overheating

and permanent equipment damage.

4x

1A

< 3.5 A (Sensor Min.)

Failure to observe the following can result in distorted product calibration:

Observe the arrow on the product showing orientation to current source.

1.

Do not expose the product to current levels greater than the maximum amperage

2.

range.

sEt-up anD Wiring

Slide Switch
Amp Ranges

0-20
0-40
0-80

Amperage Range
Selector Switch

Amp Ranges

0-20
0-40
0-80

To

Load

To

Load

4-20

mA

0-5

VDC

Gnd Power

15-24 VAC/DC

Blink=Normal
Off=No Power
Solid=Overrange

Wiring Diagram

Digital Control

(+) Power

(-) GND

0-5 VDC

4-20mA

AI

Amp Ranges

0-20
0-40
0-80

To

Load

To

Load

4-20

mA

0-5

VDC

Gnd Power

15-24 VAC/DC

Blink=Normal
Off=No Power
Solid=Overrange

scaling

SENSED AMPS

20/40/80A*

4mA/0VDC

0A

20mA/5VDC

SENSOR OUTPUT

*Slide-Switch Selectable

troublEshooting

Problem

Solution

The LED is off and no signal is

produced

Verify that power is applied to PWR (+) and GND (-)

terminals

The LED is on solid and the output

is at maximum

Verify that the amperage range selection switch is

in the proper position for the current applied to the

conductor.