beautypg.com

Caution, Installation guide, Operation – Veris Industries H721LC Install User Manual

Page 2: Troubleshooting, Wiring examples, Calibration/scaling, H721lc, External power sourcing panel (-common), Sinking panel (+common)

background image

6%2)3

INSTALLATION GUIDE

H721LC

Z202941-0C

PAGE 2

©2008 Veris Industries USA 800.354.8556 or 503.598.4564 / [email protected]

09082

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

300A:

5A

300A

5A

10A

Controller:
CT max ÷ H721LC max
300 ÷ 10 = 30x
20mA -> 300A

300 A

opEration

The H721LC is a current transducer that senses current (amperage) in any of three
field-selectable ranges: 0-10, 0-20, or 0-40 amperes. These ranges represent the
maximum current that can be applied to the monitored conductor. The H721LC
transforms the monitored current into a 4-20mA output suitable for connection to
building controllers or other appropriate data acquisition equipment. The H721LC
requires 12-30VDC external power to generate its output.

notEs

SENSED AMPS

Selected Range*

4mA

0A

20mA

SENSOR OUTPUT

*Factory calibrated ranges selected

with the amperage range switch

troublEshooting

For load currents less than sensor minimum rating:

Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the "window." This increases the current measured
by the transducer.

• Controller must be
programmed to account
for the extra turns. e.g., if
four turns pass through
the sensor (as shown) the
normal controller reading
must be divided by 4.

< 1A (H721LC min.)

0.5A

4x

10A

Controller: 0.625 A/mA + 4mA
Amps ÷ Turns
(2A ÷ 4) = 0.5A
H721LC: 2.5A max. (4T)

7.2 mA

(2A)

0.5A

DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.

Terminate the CT secondary before applying current.

H681x-5A CT

> 40A (H721LC max.)

For load currents greater than sensor maximum rating:

Use a 5 Amp (H681x series) Current Transformer (CT) as shown.

CAUTION

RISK OF EQUIPMENT DAMAGE

• Derate the product’s maximum current for the number of

turns through the sensing window using the following

formula.

Rated Max. Amps ÷ Number of Turns = Max. monitored Amps

e.g. : 30A ÷ 4 Turns = 7.5 Amps max. in monitored conductor

Failure to follow these instructions can result in overheating

and permanent equipment damage.

Problem

Solution

No Reading at Controller

•Confirm that you have 12-30VDC in series with the

sensor output terminals and the control panel analog

input.

• Confirm measured current is within the selected

range on the product.

• Check polarity of sensor output connections.

External Power

Sourcing Panel (-Common)

*A resistor can be added in parallel to convert the 4-20mA signal to a VDC signal (250 ohm=
1-5VDC); (500 ohm = 2-10VDC)

Wiring ExamplEs

DDC

CONTROLLER

PS Series

Power Supply

AI

+

+V

-V

NC

DDC

CONTROLLER

AI

COMM

4-20mA Out

+

DDC

CONTROLLER

AI

V(COM)

4-20mA
in Return

Sinking Panel (+Common)

Amperage Range
Selector Switch

calibration/scaling

Set the amperage range selector switch to a level appropriate for your load. The
H721LC is available with three choices, 0-10, 0-20, or 0-40 Amps.