Unit connection sizes, Minimum clearances, Dimensions hot water coil – York MILLENNIUM ND600 User Manual
Page 30
628767-YTG-C-0910
30
Johnson Controls Unitary Products
Unit Connection Sizes
Model
ND360
ND480
ND600
M1CZ600A
Dimensions (inches)
Length
100.1
103.1
103.1
103.1
Width
38.1
45.4
45.5
53.7
Height
74.7
89.4
45.4
54.4
System Data
No. Refrigeration Circuits
2
2
2
Suction Line OD (in.)
1 1/8
1 3/8
-
2 1/8
Liquid Line OD (in.)
7/8
7/8
-
7/8
Power Wiring Knockout
7/8
7/8
1 3/8
-
Control Wiring Knockout
7/8
7/8
7/8
-
Drain Line
7/8
7/8
-
7/8
Blower Outlet
Number
2
2
2
-
Width
19.0
19.0
24.9
-
Length
22.0
22.0
23.0
-
Return Air Inlet
Width
33.2
40.5
-
49.5
Length
95.6
98.5
-
98.5
Minimum Clearances
Top with Supply Air Opening
1
1
This dimension will vary if a supply air plenum or a base is
used.
24”
Front with Return Air Opening
24”
Right Side with access for Piping, Power & Control
Wiring Connections
2
2
This dimension is required for normal installation and service.
24”
Left Side
24”
Rear
3
3
Although no clearance is required for service and operation,
some clearance may be required for routing the power and
control wiring.
N/A
Bottom
4
4
Allow enough clearance to trap the condensate drain line.
N/A
Dimensions Hot Water Coil
Dimensions Hot Water Coil
COIL
MODEL
UNIT
MODEL
DIMENSIONS
A
B
C
D
E
F
1HW0406
ND360
100-1/8
37-7/8
6-3/4
3-7/8
1-3/8
1-3/8
1HW0407
ND480
ND600
103-1/8
45-1/4
6-1/2
4
1-5/8
1-5/8