beautypg.com

Nd360 / 1nf0454 – York MILLENNIUM ND600 User Manual

Page 16

background image

628767-YTG-C-0910

16

Johnson Controls Unitary Products

Air Handling Unit and Steam Coil Accessory Heating Capacity

NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH

ND360 / 1NF0454

UNIT

MODEL

STEAM COIL

MODEL

CAPACITY (MBH) @ 2 PSIG

1

1

These capacities do not include any blower motor heat.

CFM

DRY BULB TEMPERATURE OF AIR ENTERING COIL (°F)

10

30

50

70

ND360

1NF0454

8,000

535

483

432

380

10,000

592

535

478

422

12,000

642

580

518

456

14,000

687

621

555

489

Steam Coil Capacity Correction Factors For High Steam Pressure

STEAM PRESSURE (PSIG)

5

10

15

20

25

CAPACITY CORRECTION FACTOR

1.05

1.12

1.19

1.25

1.30

This manual is related to the following products: