Electrical specifications, Input output – Xantrex Technology GT3.0 User Manual
Page 96
![background image](/manuals/226098/96/background.png)
Specifications
A–2
975-0131-01-01
Electrical Specifications
Input
Output
Input voltage, Maximum Power Point range
195 to 550 Vdc
Absolute maximum array open circuit voltage
600 Vdc
Maximum input current
16.6 A DC
Maximum array short circuit current
19 A DC
Recommended PV array power
Up to 3300 W
Reverse polarity protection
Short circuit diode
Ground fault protection
GF detection, I
DIF
> 1 A
GT3.0 North American
GT3.0 European
Maximum output power
3000 W AC
3000 W AC
Nominal output power over rated temp range
2500 W AC
2500 W AC
Maximum utility backfeed current
20 A
20 A
Nominal output voltage
240 V
230 V
Operating range, utility voltage (default)*
*
Requires Utility permission and qualified service personnel to change settings.
211 to 264 Vac
202 to 253 Vac
Nominal output frequency
60 Hz
50 Hz
Operating range, utility frequency (default)*
59.3 to 60.5 Hz
47.1 to 50.9 Hz
Maximum continuous output current
14.2 A
14.9 A
Output overcurrent protection
20 A RMS
20 A RMS
Total Harmonic Distortion (THD)
<5%
<5%
Power factor
>0.9
>0.9
Utility monitoring—islanding protection
Vac, fac as per UL1741
Output characteristics
Current source
Output current waveform
Sine wave