Special screens – Xantrex Technology GT3.0 User Manual

Page 84

background image

Monitoring the Inverter

5–8

975-0131-01-01

Additional Fault
messages for all
systems

Additional message screens can be viewed in fault mode by tapping the Xantrex
logo near the LCD. Each additional tap displays the next screen in the order
shown in Table 5-9.

Special Screens

Special message screens are displayed in specific situations that are not
considered fault situations. They can appear in any mode of operation. These
screens are described in Table 5-10.

Table 5-9 Additional Fault Mode Screens

Tap

Display*

* In a multiple unit system with communications cables properly installed, the

system values displayed are for the entire system. Time online and array
readings are for the local inverter and PV array associated with that inverter.

Description

1st time

Current fault message
screen (see Table 5-8)

LCD backlight turns on for better readability.

2nd time

System 0W

Today 2.500kWh

Energy being produced by the system now.
Cumulative energy produced by the system
today.

3rd time

System Lifetime

305kWh

Lifetime energy produced by the GT Inverter
system.

4th time

Time Online

Today hh:mm:ss

Length of time inverter was online today, in
hours (hh), minutes (mm) and seconds (ss).

5th time

Array Readings

350.5V 8.4A

Immediate DC voltage and current readings of
power from the PV array.

6th time

Grid Readings

242.6V 60.0Hz

Immediate AC voltage and frequency readings
of power from the Grid.

Table 5-10 Special Message Screens

Display

Description

Reconnecting in

sss seconds

Time remaining in seconds (sss) before the GT Inverter
reconnects to the Grid. This is a protection timer; it runs for
approximately five minutes at startup and after any Grid fault.

Inverter

Offline

GT Inverter switching (or has switched) from Normal
Operation to Offline mode. This screen may flash alternately
with a Fault message screen.