12-1-4. Monitor Function of Remote Controller Switch

n

Call of sensor temperature display

Each sensor temperature of the remote controller, indoor
unit, and outdoor unit can become known by calling the
service monitor mode from the remote controller.

1

Push

+

buttons simultaneously for 4

seconds or more to call the service monitor
mode.

The service monitor goes on, the master indoor unit
No. is displayed, and then temperature of the item
code

00

is displayed.

2

Push the temperature setup

/

buttons

to select the sensor No. (Item code) of the sensor
to be monitored.

The sensor numbers are described below:

3

The temperature of indoor units and outdoor unit in a group control can be monitored by pushing

button to select the indoor unit to be monitored.

4

Pushing

button returns the display to usual display.

*1 Only master unit in group control

Indoor
unit data

Item code

00

01

02

03

04

Data name

Room temp (under control) *1

Room temp (remote controller)

Indoor suction temp

Indoor coil temp (TCJ)

Indoor coil temp (TC)

Outdoor
unit data

Item code

60

61

62

63

64

65

Data name

Heat exchanger temp TE

Outside temp TO

Discharge temp TD

Suction temp TS

Heat sink temp THS

UNIT

SET

CL

UNIT No.

SET DATA

R.C.

No.

4

2

1 2 3 4

3

1

Returned to usual display