beautypg.com

Toshiba RAV-SM560BT-E User Manual

Page 141

background image

– 141 –

No.

Y

Part name

Heat exchanger

Procedure

1. Detachment

1) Recover refrigerant gas.
2) Remove refrigerant pipe at the indoor

unit side.

3) Perform works of items 1 of

Q

, 1 of

R

,

1 of

S

, 1 of

T

and 1 of

W

.

4) Remove screws fixing the pipe cover.

(Ø4 x 8, 2 pcs.)

5) Remove the heat exchanger by

removing fixing band and fixing screws
while holding the heat exchanger.
(Ø4 x 8, 3 pcs.)

2. Attachment

1) Fix the parts, heat exchanger, fixing

band, pipe cover, drain cap, drain pan,
bell mouth, and electric parts box
successively to their original positions.

2) Connect connectors, earth lead wire,

indoor/outdoor inter-unit cable, and
remote controller cable which have
been disconnected in the above item 1
as before.

3) Connect the refrigerant pipe as before,

and then perform vacuuming.

Remarks

Fixing screws

Fixing band

Fixing screws

This manual is related to the following products: