Operation of diagnostic function

Check

code

Cause of operation

Inverter over-current protective
circuit operates.
(For a short time)

Status of air

conditioner

All stop

Condition

Displayed when
error is detected

Judgment and measures

1. Inverter immediately stops even if restarted.

Compressor rare short

2. Check IPDU.

Cabling error

Error mode detected by outdoor unit

All stop

All stop

All stop

All stop

All stop

All stop

All stop

All stop

All stop

All stop

Operation
continues

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Displayed when
error is detected

Error on current detection
circuit

Current value is high at AC
side even while compressor
stops.

Phase of power supply is
missed.

1. Compressor immediately stops even if restarted.

: Check IPDU.

2. Phase-missing operation of power supply

Check power voltage of R, S, T.

Coming-off, disconnection or
short of outdoor temp sensor

1. Check outdoor temp sensor (TE, TS).

2. Check CDB.

Coming-off, disconnection or
short of outdoor temp sensor

1. Check outdoor temp sensor (TD).

2. Check CDB.

Compressor drive output error

Tin thermistor temp, Tin error

(IPDU heat sink temp. is high.)

Communication error between
IPDU

Connector coming-off
between CDB and IPDU

1. Abnormal overload operation of refrigerating cycle

2. Loosening of screws and contact error of IPDU and

heat sink

3. Cooling error of heat sink

4. Check cabling of CDB and IPDU.

Compressor does not rotate.

(Over-current protective circuit
works when constant time
passed after activation of
compressor.)

1. Compressor error (Compressor lock, etc.)

: Replace compressor.

2. Cabling trouble of compressor (Phase missing)

Discharge temp error

Discharge temp over
specified value was detected.

1. Check refrigerating cycle. (Gas leak)

2. Error of electron control valve

3. Check pipe sensor (TD).

1. Check power voltage. (AC200V±20V)

2. Overload operation of refrigerating cycle

3. Check current detection circuit at AC side.

Compressor breakdown

Operation frequency lowered
and stops though operation
had started.

High-voltage protection error
by TE sensor

TE temp over specified value
was detected.

1. Overload operation of refrigerating cycle

2. Check outdoor temp sensor (TE).

DC outdoor fan motor error

IDC operation or lock was
detected by DC outdoor fan
driving.

1. Position detection error

2. Over-current protection circuit operation of outdoor fan

drive unit

Check CDB.

Refer to Judgment of outdoor fan.

1. Position detection circuit operates even if driving by

removing 3P connector of compressor.

Replace IPDU.

Error on IPDU position
detection circuit

1. Check outdoor temp sensor (TO).

2. Check P.C. board.

Coming-off, disconnection or
short of outdoor temp sensor