14-2. Troubleshooting with CHECK Display of Remote Controller

14-2-1. In case of main remote controller/sub-remote controller A

RBC-AM1E RBC-AS1E

1. Operation for CHECK display

When pushing the CHECK switch, the indoor unit No. (Group address No.) which sends the check code is
displayed at the right side of the set up TEMP. display section, and the check data of 2 errors/faults x 16 units
is displayed in the set up temp. display section.

If there is a filter display, the indoor unit No. which sends the filter signal is displayed at the right side of the
set up temp. display section, and then the check code is displayed as described above.
(1 display for 3 seconds)

LCD display “STANDBY”
is present.

• When phase-sequence of power

wiring is incorrect

• When combination of indoor units

is over capacity

• Indoor unit with command

excepted by operation mode
select switch

• When there is an indoor unit

which stopped with the indoor
overflow alarm “0b”.

• Indoor unit with cooling operation

command excepted by heating
priority control

RESET switch

Push the switch in the hole with pin.

The remote controller resets the power supply.
(All data is cleared.)

CHECK switch

Push for 0.5 seconds to display CHECK code.

Push for 3 seconds to reset indoor microprocessor.
(While indoor microprocessor is locked by ALL STOP alarm)

Push for 10 seconds to clear check data.

MODE

ON/OFF

FILTER CHECK

MODE

MODE FA N

A N

T E M P

T E M P.

AU TO
F I X

F I X

CHECK

CHECK ADDRESS

ADDRESS

UNIT

CENTRAL

1 2

F A N
C O O L

C O O L

H E AT

ST

STANDBY

ANDBY

FILTER
PREHEA

PREHEAT
DEFROST
L O U V E R
M A N UA L