Check parts. Defect Replace

* Refer to Characteristics-4.

Is not abnormal overload?

Is power voltage normal?

Is not abnormal overload?

Is charged refrigerant amount normal?

Are characteristics of

TD sensor resistance value normal?

Is the circuit detected by

current sensor normal?

Is protective control such as

discharge temprelease control normal?

Are connections of

cable/connector normal?

Correct the cabling and

connection of connector.

Improve and delete the cause

Replace TD sensor.

Improve power line.

Improve and delete the cause.

Check and correct circuit cables.

Check CDB.

Defect Replace

Check and correct the charged

refrigerant amount.

* For RAV-SM560AT-E, replace control P.C. board.

Check IPDU.

Defect Replace

* For RAV-SM560AT-E, replace control P.C. board.

NO

NO

NO

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

YES

[P03 error]/[1E error]

[H01 error]/[1F error]