[Mounting]

In case of AIK-PXXXH series

1. As same as P.C. board before replacement, attach a cable (Black) which is screwed to the electric parts

box to CN240 without using a cable (Black) attached previously to CN240 of the service P.C. board.

Service P.C. board

Cable

(Remove a cable
attached previously
to CN240 of the
service P.C. board.)

CN204

2. Attach other cables as same as P.C. board before replacement.

Part name

SW03

1

2

Function

TA shift: Thermo-OFF point can be shifted in heating operation.

Bit 1

Bit 2

OFF

OFF

OFF

ON

ON

OFF

ON

ON

Shift Q’ty

+ 6K

+ 4K

+ 2K (Setup at shipment)

± 0K

Selection of hot start control temperature :
The starting temperature of the fan can be raised in heating operation.

J09

Provided

None

Setup

Normal (Setup at shipment)

Fan starting temp up (Approx. +4K)

Setup of filter timer

J11

J12

Provided

Provided

None

Provided

Provided

None

None

None

Setup

240 hours (Setup at shipment)

2500 hours

5000 hours

Without filter timer

J09

J11
J12

<(Reference) Explanation about functions of switches/jumpers>

The following table shows the functions of the main switches and jumpers. Use as reference in miss-setup.