Air volume control
(Continued)

Outline of specifications

Remarks

6

Tap

F4

F5

F6

F7

F8

F9

FA

FB

FC

FD

Air volume setup

COOL, DRY, FAN

HEAT

UH

H

H

M+

M+

M

M

L+

L+

L

L

UL

SM560

SM800

Revolutions per

minute (rpm)

1290

1480

1230

1480

1180

1340

1150

1320

1120

1310

1060

1200

1060

1200

990

1100

940

1040

900

900

3) In heating operation, the mode changes to [Ultra

Low (UL)] or [STOP] if thermostat is turned off.

4) If Ta

25

°

C when heating operation has started and

when defrost operation has been cleared, it oper-
ates with MED mode or higher mode for 1 minute
from when Tc has entered in A zone of cool air
discharge preventive control (Item 6).

5) In automatic cooling/heating operation, the revolu-

tion frequency of [HIGH (H)] is set larger than that in
the standard cooling/heating operation. However the
revolution frequency is restricted in the automatic
heating operation as shown in the following figure.

Stop

is a

cool air

discharge preventive
control

operation by Tc.

Tc: Indoor heat exchanger
sensor temp.

Display: [AUTO]

6) (For wireless type only) The mode enters [AUTO] in

automatic cooling/heating operation.

7) The mode enters [LOW (L)] during Dry operation

1) In heating operation, the indoor fan is controlled

based on the detected temperature of Tc sensor.
As shown below, the upper limit of the revolution
frequency is determined.

A zone : Setup air volume

from remote
controller

B zone : Low air
C zone : OFF

Cool air discharge
preventive control

Display in C zone

Display of main unit:
Defrost LED goes on.

When wired remote
controller is installed:
PRE-HEAT/DEFROST
goes on remote controller.

F5

F4

47

42

F4

Tc

(

C)

30

26

20

16

Tc(

C)

A

B

C