F287, F271, F272 – Toshiba H9 User Manual
Page 139: F273, F274, F275

H9 ASD Installation and Operation Manual
131
Jump Frequency 1 Bandwidth
Program
⇒
Special
⇒
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #1 (see
).
Direct Access Number — F271
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Jump Frequency 2
Program
⇒
Special
⇒
Jump Frequencies
Same as Jump Frequency #1 (
) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at
). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.
Direct Access Number — F272
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
Units — Hz
Jump Frequency 2 Bandwidth
Program
⇒
Special
⇒
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #2
(
Direct Access Number — F273
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency 3
Program
⇒
Special
⇒
Jump Frequencies
Same as Jump Frequency #1 (
) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at
When multiple jump frequencies overlap, the system will recognize the lowest
and the highest frequencies as one jump range.
Direct Access Number — F274
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
Units — Hz
Jump Frequency 3 Bandwidth
Program
⇒
Special
⇒
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency #3
(
Direct Access Number — F275
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Preset Speed 8
Program
⇒
Frequency
⇒
Preset Speeds
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed #8. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed (see
for more information on
this parameter).
Direct Access Number — F287
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — Lower Limit (
Maximum — Upper Limit (
)
Units — Hz