beautypg.com

Transfer modes, Ransfer, Odes – RayTek 54301 User Manual

Page 74: Programming guide, 1 transfer modes, 66 mid

background image

Programming Guide

 

11.1 Transfer Modes 

The unit’s serial interface is either RS232 or RS485, depending on the 
model. 
Settings: 

transfer  rate:  9.6  kBaud,  8  data  bits,  1  stop  bit,  no 
parity, flow control: none (half duplex mode). 

There are two possible transfer modes for the serial interface: 
Poll Mode:  By  user  interface  control,  a  parameter  will  be  set  or 

requested. 

Burst Mode:  A  pre‐defined  data  string  (“burst  string“)  will  be 

transferred as fast as possible as long as the burst mode 
is  activated.  The  data  will  be  transferred  in  one 
direction only, from the unit to the user interface. 

 
V=P 

“P“  starts  the  Poll  mode  (allows  to  request  or  to  set 
parameters) 

V=B 

“B“ starts the Burst mode (data will be transferred as 
fast as possible; necessary: data string definition – 
“Burst string“) 

$=UTIE 

“$“ sets the parameter combination (“burst string“) 

 

“U“ unit (°C or °F) 

 

“T“ temperature value 

 

“I“ internal temperature of the sensing head 

 

“E“ emissivity 

?X$ 

gives the burst string parameters while in poll mode 

 
Return from the burst mode to the poll mode: 
If the poll mode shall be activated while the burst mode is still active, 
send  a  character  and  within  the  following  3  seconds  the  command 
V=P. 

66 

MID