RuggedCom RUGGEDBACKBONE RX1510 User Manual
Page 46
Chapter 5
EMI And Environmental Type Tests
RuggedBackbone™ RX1510
Installation Guide
40
Test
Description
Test Levels
Severity
Levels
A.C. Power ports
2.5kV common, 1kV
diff. mode@1MHz
3
Signal ports
30V Continuous, 300V for 1s
4
IEC 61000-4-16
Mains Frequency Voltage
D.C. Power ports
30V Continuous, 300V for 1s
4
IEC 61000-4-17
Ripple on D.C.
Power Supply
D.C. Power ports
10%
3
Signal ports
2kVAC (Fail-Safe Relay output)
N/A
D.C. Power ports
1.5kVDC
N/A
IEC 60255-5
Dielectric Strength
A.C. Power ports
2kVAC
N/A
Signal ports
5kV (Fail-Safe Relay output)
N/A
D.C. Power ports
5kV
N/A
IEC 60255-5
H.V. Impulse
A.C. Power ports
5kV
N/A
a
RuggedCom-specified severity levels
Table 26: IEEE 1613 (C37.90.x) EMI Immunity Type Tests
b
Test
Description
Test Levels
Enclosure Contact
+/-2kV, +/-4kV, +/- 8kV
IEEE C37.90.3
ESD
Enclosure Air
+/-4kV, +/-8kV, +/-15kV
IEEE C37.90.2
Radiated RFI
Enclosure ports
35 V/m
Signal ports
+/- 4kV @ 2.5kHz
D.C. Power ports
+/- 4kV
A.C. Power ports
+/- 4kV
IEEE C37.90.1
Fast Transient
Earth ground ports
+/- 4kV
Signal ports
2.5kV common mode @1MHz
D.C. Power ports
2.5kV common, 1kV diff. mode@1MHz
IEEE C37.90.1
Oscillatory
A.C. Power ports
2.5kV common, 1kV diff. mode@1MHz
Signal ports
5kV (Fail-Safe Relay output)
D.C. Power ports
5kV
IEEE C37.90
H.V. Impulse
A.C. Power ports
5kV
Signal ports
2kVAC
D.C. Power ports
1.5kVDC
IEEE C37.90
Dielectric Strength
A.C. Power ports
2kVAC
b
Meets Class 2 requirements for an all-fiber configuration. Meets Class 1 requirements for copper ports.
Table 27: Environmental Type Tests
Test
Description
Test Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40°C, 16 Hours