Changing the flue outlet – Raypak 302B-902B User Manual

Page 27

background image

27

8. Locate and guard vent termination to prevent acci-

dental contact by people or pets.

9. DO NOT terminate vent in window well, stairwell,

alcove, courtyard or other recessed area.

10. DO NOT terminate above any door, window, or

gravity air intake. Condensate can freeze, causing

ice formations.

11. Locate or guard vent to prevent condensate from

damaging exterior finishes. Use a rust-resistant

sheet metal backing plate against brick or mason-

ry surfaces.

12. DO NOT extend exposed vent pipe outside of

building. Condensate could freeze and block vent

pipe.

U.S. Installations

Refer to the latest edition of the National Fuel Gas

Code.

Vent termination requirements are as follows:

1. Vent must terminate at least 4 ft below, 4 ft hori-

zontally from or 1 ft above any door, window or

gravity air inlet to the building.

2. The vent must not be less than 7 ft above grade

when located adjacent to public walkways.

3. Terminate vent at least 3 ft above any forced air

inlet located within 10 ft.

4. Vent must terminate at least 4 ft horizontally, and

in no case above or below unless 4 ft horizontal

distance is maintained, from electric meters, gas

meters, regulators, and relief equipment.

5. Terminate vent at least 6 ft away from adjacent

walls.

6. DO NOT terminate vent closer than 5 ft below roof

overhang.

7. The vent terminal requires a 12 in. vent terminal

clearance from the wall.

8. Terminate vent at least 1 ft above grade, including

normal snow line.

9. Multiple direct vent installations require a 4 ft

clearance between the ends of vent caps located

on the same horizontal plane.

Canadian Installations

Refer to latest edition of the B149 Installation code.

A vent shall not terminate:

1. Directly above a paved sidewalk or driveway

which is located between two single-family dwell-

ings and serves both dwellings.

2. Less than 7 ft (2.13 m) above a paved sidewalk or

paved driveway located on public property.

3. Within 6 ft (1.8 m) of a mechanical air supply inlet

to any building.

4. Above a meter/regulator assembly within 3 ft (915

mm) horizontally of the vertical centre-line of the

regulator.

5. Within 6 ft (1.8 m) of any gas service regulator

vent outlet.

6. Less than 1 ft (305 mm) above grade level.

7. Within the 3 ft (915 mm) of a window or door which

can be opened in any building, any non-mechani-

cal air supply inlet to any building or the

combustion air inlet of any other appliance.

8. Underneath a verandah, porch or deck, unless the

verandah, porch or deck is fully open on a mini-

mum of two sides beneath the floor, and the

distance between the top of the vent termination

and the underside of the verandah, porch or deck

is greater than 1 ft (305 mm).

Changing the Flue Outlet

Follow these instructions to change the flue connec-

tion from the standard top location to the rear of the

heater (when the optional vent tee is ordered).

1. Disconnect all electrical power from the heater (if

applicable).

2. Disconnect or isolate the main gas pipe from the

heater (if applicable).

3. Remove the screws, gasket and dustcover from

the rear of the heater.

4. Remove the screws, stainless steel flue cover and

gasket from the branch side of the tee located in

the flue box at the rear of the heater.