beautypg.com

Conventional combustion air supply, Conventional combustion air supply 13 – Raypak 302B-902B User Manual

Page 13

background image

13

three or four sheet metal screws (not supplied) equal-

ly distributed around the circumference of the duct. All

ducting should be self-supported. The filter housing is

not designed to support the air duct.

TruSeal™ Combustion Air

In certain applications it may be necessary to utilize

the TruSeal option (sales order option D-21 or D-22)

and duct the combustion air directly to the blower.

Combustion air may be ducted directly to the heater by

using PVC, CPVC or sealed single-wall galvanized

ducting. The duct will attach directly to the air collar lo-

cated on the side of the heater, using three or four

sheet metal screws (not supplied) equally positioned

around the circumference of the duct. The screws and

duct connection point must be sealed with RTV (not

supplied). An in-line intake air filter kit (sales order

option D-17) must be installed in the combustion air

duct. TruSeal is generally used when damaging con-

taminants are present in the mechanical room.

TruSeal heater connection points are available as fol-

lows:

302B & 402B Right side only

502B to 902B Left side - standard

Right side - optional

Conventional Combustion Air

Supply

U.S. Installations

All Air from Inside the Building

The confined space shall be provided with TWO per-

manent openings communicating directly with an

additional room(s) of sufficient volume so that the com-

bined volume of all spaces meets the criteria for a

room large in comparison (NFGC). The total input of all

gas utilization equipment installed in the combined

CAUTION: Use TrueSeal combustion air if

damaging airborne contaminants are or will be

present in the heater area. See the Appendix

regarding air contamination.

space shall be considered in making this determina-

tion. Each opening shall have a minimum free area of

1 in.

2

per 1,000 BTUH (2,225 mm

2

per kW) of the total

input rating of all gas utilization equipment in the con-

fined space, but not less than 100 in.

2

(645 cm

2

). One

opening shall commence within 12 in. (305 mm) of the

top, and one opening shall commence within 12 in.

(305 mm) of the bottom of the enclosure. The mini-

mum dimension of air openings shall be not less than

3 in. (76 mm) in any direction.

All Air from Outdoors

The confined space shall communicate with the out-

doors in accordance with one of the methods below.

The minimum dimension of air openings shall not be

less than 3 in. (76 mm) in any direction. Where ducts

are used, they shall be of the same cross-sectional

area as the net free area of the openings to which they

connect.

1. Two permanent openings, one commencing

within 12 in. (305 mm) of the top, and one com-

mencing within 12 in. (305 mm) of the bottom of

the enclosure, shall be provided. The openings

shall communicate directly, or by ducts, with the

outdoors or spaces (crawl or attic) that freely com-

municate with the outdoors.

a. Where directly communicating with the out-

doors or where communicating to the

outdoors through vertical ducts, each opening

shall have a minimum free area of 1 in.

2

per

4,000 BTUH (550 mm

2

per kW) of total input

rating of all equipment in the enclosure.

b. Where communicating with the outdoors

through horizontal ducts, each opening shall

have a minimum free area of 1 in.

2

per 2,000

BTUH (1,100 mm

2

per kW) of total input rat-

ing of all equipment in the enclosure.

2. One permanent opening, commencing within 12

in. (305 mm) of the top of the enclosure, shall be

permitted where the equipment has clearances of

at least 1 in. (25 mm) from the sides and back and

6 in. (152 mm) from the front of the appliance. The

opening shall directly communicate with the out-

doors or shall communicate through a vertical or

horizontal duct to the outdoors or spaces that

freely communicate with the outdoors, and shall

have a minimum free area of:

a. 1 in.

2

per 3,000 BTUH (740 mm

2

per kW) of

the total input rating of all equipment located in

the enclosure, and

CAUTION: This type of installation is

recommended if damaging airborne contaminants

are or will be present in the heater area. See the

Appendix regarding air contamination.