Powerware UPS Sidecar Powerware 9390 User Manual
Page 72
POWER WIRING INSTALLATION NOTES
092107
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
D
164201546---4
6 of 10
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual
S 164201586 Rev E www.powerware.com
A-22
Table I. UPS Sidecar Maintenance Bypass Power Cable Terminations
80/40, 80/50, 80/60, 80/80, 208/208V and 160/100, 160/120, 160/160, 480/480V
Terminal Function
Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type
Screw
AC Input to Maintenance
Bypass or Optional BIB
Phase A 1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16” Hex
3/8” Hex
Phase B 1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16” Hex
3/8” Hex
Phase C 1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16” Hex
3/8” Hex
AC Input to Optional RIB
Phase A 1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16” Hex
3/8” Hex
Phase B 1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16” Hex
3/8” Hex
Phase C 1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16” Hex
3/8” Hex
AC Output to Critical Load Phase A 1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16” Hex
3/8” Hex
Phase B 1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16” Hex
3/8” Hex
Phase C 1 --- 2/0---250 kcmil
1 --- 2/0---500 kcmil
31.1 (275)
31.1 (275)
5/16” Hex
3/8” Hex
Table J. UPS Sidecar 1+1 Parallel Redundant Power Cable Terminations
40/20, 40/30, 40/40, 208/208V and 80/40, 80/50, 80/60, 80/80, 480/480V
Terminal Function
Function
Size of Pressure
Termination
Tightening Torque
Nm (lb in)
Type
Screw
AC Input from UPM2 to
MOB 2 (standalone
installation)
Phase A 1 --- #4---350 kcmil
20.3 (180)
3/16” Hex
Phase B 1 --- #4---350 kcmil
20.3 (180)
3/16” Hex
Phase C 1 --- #4---350 kcmil
20.3 (180)
3/16” Hex
AC Output to Critical Load
(without SLB) Terminal
Block
Phase A 1 --- #14---2/0
13.5 (120)
3/16” Hex
Phase B 1 --- #14---2/0
13.5 (120)
3/16” Hex
Phase C 1 --- #14---2/0
13.5 (120)
3/16” Hex
AC Output to Critical Load
(with SLB)
Phase A 1 --- #4---350 kcmil
20.3 (180)
3/16” Hex
Phase B 1 --- #4---350 kcmil
20.3 (180)
3/16” Hex
Phase C 1 --- #4---350 kcmil
20.3 (180)
3/16” Hex
Neutral (80/480)
Neutral
4 --- #14---1/0
5.6 (50)
Slotted
Neutral (40/208)
Neutral
8 --- #6---250 kcmil
42.4 (375)
5/16” Hex
Ground
Ground
2 --- #14---1/0
5.6 (50)
Slotted