POWER WIRING INSTALLATION NOTES

092107

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

D

164201546---4

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com

A-17

Table B

.

INPUT/OUTPUT Ratings & External Wiring Requirements for

Powerware 9390 UPS Sidecar (Maintenance Bypass) 208/208V

Units

Rating 50/60 Hz

Basic Unit Rating

UPS kVA

20

30

40

50

60

80

Input and Bypass Input

Output

VOLTS

VOLTS

208

208

208

208

208

208

208

208

208

208

208

208

AC Input to Maintenance Bypass (without

BIB or RIB, or dual feed with BIB and RIB)

(3) Phases, (1) Neutral---if required,

(1) Ground

A

AMPS

56

83

111

139

167

222

Minimum Conductor Size

Number per Phase

AWG or kcmil

(each)

2

(1)

2/0

(1)

2/0

(1)

4/0

(1)

250

(1)

2/0

(2)

AC Input to Maintenance Bypass (single

feed with BIB, or single feed with BIB and RIB)

(3) Phases, (1) Neutral---if required,

(1) Ground

A

AMPS

60

90

125

155

185

240

Minimum Conductor Size

Number per Phase

AWG or kcmil

(each)

2

(1)

2/0

(1)

2/0

(1)

4/0

(1)

250

(1)

2/0

(2)

AC Input to Optional RIB

(3) Phases, (1) Ground

B

AMPS

60

90

125

155

185

240

Minimum Conductor Size

Number per Phase

AWG or kcmil

(each)

2

(1)

2/0

(1)

2/0

(1)

4/0

(1)

250

(1)

2/0

(2)

AC Output to Critical Load

Full Load Current
(3) Phases, (1) Neutral---if required,

(1) Ground

C

AMPS

56

83

111

139

167

222

Minimum Conductor Size

Number per Phase

AWG or kcmil

(each)

2

(1)

2/0

(1)

2/0

(1)

4/0

(1)

250

(1)

2/0

(2)

NOTE Callout letters

A, B,

and

C

map to drawing 164201546---3, sheets 1 of 11,

5 of 11, and 9 of 11.