POWER WIRING INSTALLATION NOTES
092107
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
D
164201546---4
3 of 10
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual
S 164201586 Rev E www.powerware.com
A-19
Table D. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9390 UPS Sidecar (1+1 Parallel Redundant) 208V
Units
Rating 50/60 Hz
Basic Unit Rating
UPS kVA
40
50
60
80
Input and Bypass Input
Output
VOLTS
VOLTS
208
208
208
208
208
208
208
208
AC Input from UPM
Full Load Current for each Module
(3) Phases, (1) Neutral---if required, (1) Ground
—
AMPS
111
139
167
222
Minimum Conductor Size for each Module
Number per Phase for each Module
For customer-supplied wiring in a standalone
installation, refer to the applicable Powerware 9390
installation and operation manual, listed in paragraph
1.5, for wire size. Wiring for line-up-and-match
installation is factory-supplied.
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral---if required, (1) Ground
D
AMPS
111
139
167
222
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(1)
4/0
(1)
250
(1)
2/0
(2)
NOTE Callout letter
D
maps to drawing 164201546---3, sheet 11 of 11.
Table E. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9390 UPS Sidecar (1+1 Parallel Redundant) 480V
Units
Rating 50/60 Hz
Basic Unit Rating
UPS
kVA
20
(See
Note 2)
30
(See
Note 2)
40
50
60
80
100
120
160
Input and Bypass Input
Output
VOLTS
VOLTS
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
AC Input from UPM
Full Load Current for each Module
(3) Phases, (1) Neutral---if required,
(1) Ground
—
AMPS
48
48
48
60
72
96
120
144
192
Minimum Conductor Size for each
Module
Number per Phase for each Module
For customer-supplied wiring in a standalone installation, refer to the applicable
Powerware 9390 installation and operation manual, listed in paragraph 1.5, for wire
size. Wiring for line-up-and-match installation is factory-supplied.
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral---if required,
(1) Ground
D
AMPS
48
48
48
60
72
96
120
144
192
Minimum Conductor Size
Number per Phase
AWG or
kcmil
(each)
4
(1)
4
(1)
4
(1)
2
(1)
1
(1)
1/0
(1)
4/0
(1)
4/0
(1)
1/0
(2)
NOTE 1. Callout letter
D
maps to drawing 164201546---3, sheet 11 of 11.
NOTE 2. 40/20 kVA and 40/30 kVA parallel systems must be wired same as a 40/40 kVA.