PHYSICAL FEATURES AND REQUIREMENTS
031505
A
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual
S 164201586 Rev E www.powerware.com
A-5
1.
The UPS Sidecar equipment operating environment must meet the weight requirements
shown in the applicable Powerware 9390 installation and operation manual, listed in
paragraph 1.5, plus 150 pounds for the UPS Sidecar. Size requirements are shown in
Drawing 164201546---8 starting on page A---68.
2.
Do not tilt cabinets more than 10˚ during handling.
3.
Dimensions are in millimeters (inches).
4.
The clearances required around the UPS Sidecar cabinet are shown in Table A.
Table A. UPS Sidecar Clearances
From Top of Cabinet
Minimum clearance over the UPS Sidecar is
457.2 mm (18”) for ventilation
From Front of Cabinet
914.4 mm (36”) working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
5.
The basic environmental requirements for operation of the UPS Sidecar are:
Ambient Temperature Range:
0---40˚C (32---104˚F)
Recommended Operating Range: 20---25˚C (68---77˚F)
Maximum Relative Humidity:
95% noncondensing