beautypg.com

Powerware UPS Sidecar Powerware 9390 User Manual

Page 57

background image

UPS SIDECAR ONELINE DRAWINGS

062806

B

DESCRIPTION:

DATE:

DRAWING NO:

SHEET:

REVISION:

MAINTENANCE BYPASS CONFIGURATION

120/100 AND 120/120 kVA, 480/480V

160/100, 160/120, AND 160/160 kVA, 480/480V

WITH UPS SERIAL NUMBER SEVENTH DIGIT AT “A”

K1

K5

K3

Powerware 9390 UPS CABINET

UPS Sidecar

MAINTENANCE

BYPASS SWITCH

(MBP)

AC INPUT

TO BYPASS

A

MAINTENANCE

ISOLATION SWITCH

(MIS)

AC INPUT

TO UPS

E1, E2, E3

SINGLE-FEED

JUMPER

(REMOVE FOR

DUAL-FEED)

E6, E7,

E8, E12

C

AC OUTPUT

TO

CRITICAL LOAD

E4. E5

BATTERY

CONVERTER

INVERTER

RECTIFIER

NOTE

1. A minimum of two separate feeds with

upstream feeder breakers, or one feed

with two upstream feeder breakers, must

be provided: one for the UPS and one for

the UPS Sidecar bypass input. DO NOT

use one feed or a single feeder breaker to

supply both the UPS and the UPS

Sidecar

.

2. Remove jumper for dual-feed.

3. If the load requires a neutral, a bypass

neutral feeder must be supplied.

SERIAL NUMBER SEVENTH

DIGIT AT “A”

2 of 11

164201546---3

E6, E7, E8

E9, E10, E11

INSTALLATION INFORMATION

EATON Powerware

®

9390 UPS Sidecar Installation and Operation Manual

S 164201586 Rev E www.powerware.com

A-7