Powerware UPS Sidecar Powerware 9390 User Manual
Page 115

063006
D
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
UPS SIDECAR TERMINAL TB1 FOR
PARALLEL REDUNDANT
CONFIGURATIONS
1
10
TB1
NOT USED
NOT USED
INTERFACE AND CONTROL WIRING
INSTALLATION NOTES AND
TERMINAL LOCATIONS
NOTE 1.
Alarm displays as Building Alarm 2 on the UPS Control Panel
Display Screen, unless the alarms are programmed to display the
alarm functional name.
2.
Use twisted-pair wires for each alarm input and common.
MOB 1 AUX 1 CONTACT COMMON
MOB 1 AUX 1 CONTACT NC
MOB 1 AUX 2 CONTACT NO
MOB 2 AUX 1 CONTACT NC
MOB 2 AUX 2 CONTACT NO
MOB 1 AUX 2 CONTACT COMMON
MOB 2 AUX 1 CONTACT COMMON
MOB 2 AUX 2 CONTACT COMMON
2 of 4
164201546---7
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual
S 164201586 Rev E www.powerware.com
A-65