UPS SIDECAR ONELINE DRAWINGS
062806
B
MAINTENANCE BYPASS WITH BIB CONFIGURATION
120/100 AND 120/120 kVA, 480/480V
160/100, 160/120, AND 160/160 kVA, 480/480V
WITH UPS SERIAL NUMBER SEVENTH DIGIT AT “A”
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
K1
K5
K3
Powerware 9390 UPS CABINET
UPS Sidecar
MAINTENANCE
BYPASS SWITCH
(MBP)
AC INPUT
TO BYPASS
A
MAINTENANCE
ISOLATION SWITCH
(MIS)
BYPASS INPUT
BREAKER (BIB)
SINGLE-FEED
JUMPER
(REMOVE FOR
DUAL-FEED)
C
AC OUTPUT
TO
CRITICAL LOAD
E4. E5
BATTERY
CONVERTER
INVERTER
RECTIFIER
NOTE
1. Remove jumper for dual-feed.
2. If the load requires a neutral, a bypass
neutral feeder must be supplied.
SERIAL NUMBER SEVENTH
DIGIT AT “A”
164201546---3
6 of 11
E6, E7, E8
E9, E10, E11
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual
S 164201586 Rev E www.powerware.com