POWER WIRING INSTALLATION NOTES
061507
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
D
164201546---4
2 of 10
INSTALLATION INFORMATION
EATON Powerware
®
9390 UPS Sidecar Installation and Operation Manual
S 164201586 Rev E www.powerware.com
A-18
Table C
.
INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware 9390 UPS Sidecar (Maintenance Bypass) 480/480V
Units
Rating 50/60 Hz
Basic Unit Rating
UPS kVA
20
30
40
50
60
80
100
120
160
Input and Bypass Input
Output
VOLTS
VOLTS
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
480
AC Input to Maintenance
Bypass (without BIB or RIB, or
dual feed with BIB and RIB)
(3) Phases, (1) Neutral---if required,
(1) Ground
A
AMPS
24
36
48
60
72
96
120
144
193
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
6
(1)
4
(1)
4
(1)
2
(1)
1
(1)
1/0
(1)
4/0
(1)
4/0
(1)
1/0
(2)
AC Input to Maintenance
Bypass (single feed with BIB, or
single feed with BIB and RIB)
(3) Phases, (1) Neutral---if required,
(1) Ground
A
AMPS
30
40
55
67
80
105
130
160
210
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
6
(1)
4
(1)
4
(1)
2
(1)
1
(1)
1/0
(1)
4/0
(1)
4/0
(1)
1/0
(2)
AC Input to Optional RIB
(3) Phases, (1) Ground
B
AMPS
30
40
55
67
80
105
130
160
210
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
6
(1)
4
(1)
4
(1)
2
(1)
1
(1)
1/0
(1)
4/0
(1)
4/0
(1)
1/0
(2)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Neutral---if required,
(1) Ground
C
AMPS
24
36
48
60
72
96
120
144
193
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
6
(1)
4
(1)
4
(1)
2
(1)
1
(1)
1/0
(1)
4/0
(1)
4/0
(1)
1/0
(2)
NOTE Callout letters
A, B,
and
C
map to drawing 164201546---3, sheets 1 of 11,
2 of 11, 3 of 11, 4 of 11, 5 of 11, 6 of 11, 7 of 11, 8 of 11, and 9 of 11.