beautypg.com

Ac input, Dc circuit, Ac output – Powerware 9155 UPS20-30kVA User Manual

Page 51

background image

1

UPS 20-30 kVA, 230 V 0/60 Hz output

User’s Guide

1026743
Revision B

AC input

Powerware 9155

20 kVA

30 kVA

Rectifier input

3 phases + N

Bypass input

1 phase + N

Voltage (L-N)

192 to 276 Volts without using battery

Frequency

45 to 65 Hz

Power factor

0.99

Input distortion

< 5% THD(I)

Rated input current

29 A

43 A

DC circuit

Powerware 9155

20 kVA

30 kVA

Management

Advanced Battery Management

Nominal voltage

432 Volts

Battery qty

36 / string

Float voltage

2.30 VPC

Battery type

VRLA 12 Volts

Cut off voltage

1.75 VPC

Battery charging

6 A (default), user selectable

AC output

Powerware 9155

20 kVA

30 kVA

Active power

18 kW

27 kW

Number of phases

1-phase + N

Frequency

50 Hz or 60 Hz, user selectable

Voltage (L-N)

220, 230 or 240 Volts, user selectable

Short circuit capability

300 A < 300 ms

Overload capability

10 min > 100 – 110% load

1 min > 110 – 125% load

5 sec > 125 – 150% load

300 ms > 150% load

Overload capability

(mains available)

60 min > 100 – 110% load

10 min > 110 – 125% load

1 min > 125 – 150% load