Planning before installation – Powerware 9155 UPS20-30kVA User Manual

Page 12

background image

12

UPS 20-30 kVA, 230 V 0/60 Hz output

User’s Guide

1026743

Revision B

4. Planning before installation

The equipment must be installed in upright position. The equipment requires space to front and
back to enable cooling airflow. Service and maintenance require 00 mm clearance on right
hand side. All cooling air enters at front and exits at unit rear. The required min. clearance from
unit rear to an obstruction is 20 mm. Because the service and user access is in the front there
should be reserved enough space (min 600 mm).

It is required to arrange ventilation of the UPS room. Sufficient amount of air cooling is needed
to keep the max. room temperature rise at desired level:

Temperature rise of max. +°C requires the airflow of 600 m

3

per 1 kW of losses.

Temperature rise of max. +10°C requires the airflow of 300 m

3

per 1 kW of losses.

An ambient temperature of 1 to 2 Celsius degrees is recommended to achieve a long life of
the UPS and batteries. The cooling air entering the UPS must not exceed +40 °C. Avoid high
ambient temperature, moisture and humidity.

The floor material should be non-flammable and strong enough to support the heavy load. The
UPS has (4) leveling feet that should be used when finalising the installation. The diameter of a
single leveling foot is 29 mm.

Equipment

Weight

Point

Distributed

Note

20-30 kVA

20-30 kVA

20-30 kVA

UPS w/o BAT

200 kg

7.57 kg/cm

2

531 kg/m

2

No Batteries installed

UPS+1 BAT

300 kg

11.35 kg/cm

2

797 kg/m

2

1 Battery string installed

UPS+2 BAT

400 kg

15.14 kg/m

2

1063 kg/m

2

2 Battery strings installed

UPS+3 BAT

500 kg

18.92 kg/cm

2

1328 kg/m

2

3 Battery strings installed

UPS+4 BAT

600 kg

22.71 kg/cm

2

1594 kg/m

2

4 Battery strings installed

EXT BAT 0

150 kg

5.67 kg/cm

2

401 kg/m

2

No Batteries installed

EXT BAT 1

510 kg

19.29 kg/cm

2

1362 kg/m

2

1 Battery string installed

EXT BAT 2

870 kg

32.90 kg/cm

2

2323 kg/m

2

2 Battery strings installed

Table 1 The floor surface must tolerate loading.