UPS 20-30 kVA, 230 V 0/60 Hz output

User’s Guide

1026743

Revision B

User Settings

The UPS has the following typical settings that are user configurable. Note that some of the
settings become effective at the next start-up of the UPS. User settings can configured via the
front panel. Select: SETTINGS -> USER SETTINGS.

Description

Available settings

Default setting

General:
Display contrast adjustment

+ / -

Moderate

Display language

[English], [Spanish], [French], [German]

English (British)

Date & time

[xxxx-xx-xx]

0001-01-01

Audible alarms

[Normal], [Disabled]

Normal

Normal screen in display

[logo], [mimic]

Product name

User settings password

[Not required], [Set]

Not required

Nominal values:
Nominal output voltage (L-N)

[220], [230], [240]

230 Volts

Nominal output frequency

[50 Hz], [60 Hz]

50 Hz

Rectifier phase current limit

Step: 1 A

56 A

Communication and connectivity:
Disable control commands

[Enabled], [Disabled]

Disabled

Communication speed

[1200], [2400], [9600], [19200]

19200 bps.

Std. relay output function

[UPS ON/OK], [Custom], [Battery low],

[System on bypass], [System on battery]

UPS ON/OK

Signal input #1-2 function

[Empty], [see Signal inputs]

Empty

Hardware remote off delay for hardware

Remote off with restart function.

Step: 1 sec.

120 sec

XSlot relay output 1-4 function

[Nothing], [see Signal inputs]

XSlot defaults:

#1: on battery

#2: battery low

#3: UPS on/ok

#4: on bypass

XSlot input signal (long break via Rx)

Nothing

XSlot shutdown signal activation delay before

the signal is accepted.

Step: 1 sec.

5 sec

Bypass and syncronisation:
Usage of bypass

[Enabled], [Disabled]

Enabled

Require synch at transfer on bypass

[Required], [Not Required]

Not required

Transfer on bypass on overload

[Immediately], [after delay]

Immediately

Synchronization enable

[Enabled], [Disabled]

Enabled

Bypass voltage deviation high limit

+1% ... +20%, step: 1%

+10%

Bypass voltage deviation low limit

-1% ... -20%, step: 1%

-15%

Synchronization window

0.5 ... 3.0 Hz, step: 0.1 Hz

±2.0 Hz

Frequency slew rate (not in parallel mode)

0.1 ... 3.0 Hz/s, step 0.1 Hz/s

0.2 Hz/s