UPS 20-30 kVA, 230 V 0/60 Hz output

User’s Guide

1026743

Revision B

13. Technical data

Standards

UPS

20 kVA

30 kVA

Safety

IEC 62040-1-1, EN 62040-1-1 and EN 60950

EMC

EN 50091-2

Product

IEC 62040-3 and EN 62040-3

Environment

UPS

20 kVA

30 kVA

Amb. temperature

0 to +40°C (electronics), 15 to +25°C (batteries)

Relative humidity

0 to 95%, no condensation allowed

Altitude

<1000 m above sea level

Vibration

IEC 68-2-6; max. 0.3 mm (2 to 9 Hz), max. 1 m/s2 (9 to 200 Hz) sinusoidal

Maintenance configuration

UPS

20 kVA

30 kVA

Dimensions

- Width

- Depth

- Height

494 mm

762 mm

1684 mm

Weight

- no battery

- 36 battery

- 72 battery

- 108 battery

- 144 battery

200 kg

300 kg

400 kg

500 kg

600 kg

Colour

RAL 9005 black

Characteristics

Powerware 9155

20 kVA

30 kVA

Efficiency

- nominal load

Up to 93%

Up to 93%

Heat losses

<1600 W

<1900 W

Backup time

- load pf 0.7

- temperature 25°C

5 min (36 bat 9Ah)

13 min (72 bat 9Ah)

22 min (108 bat 9Ah)

31 min (144 bat 9Ah)

-

7 min (72 bat 9Ah)

13 min (108 bat 9Ah)

20 min (144 bat 9Ah)

Noise (ISO 7779)

50 - 53 dB(A) depending on the load

50 - 53 dB(A) depending on the load