Powerware 9155 UPS20-30kVA User Manual

Page 31

background image

31

UPS 20-30 kVA, 230 V 0/60 Hz output

User’s Guide

1026743
Revision B

Battery information and settings:
ABM charging cycling disable

[Enabled], [Disabled]

Enabled

Charging temp compensation

[Enabled], [Disabled]

Enabled

Battery size setting

Step: 1 Watts/cell

24 Watts/cell

Number of 36 pcs. battery strings

0 (no batteries), 1, 2, 3, 4...

1 string

Battery low alarm level

Step: 0.01 V/cell

1.88 V/cell

Automatic battery support test

[Enabled], [Disabled]

Enabled

Maximum charging current

Step: 0.1 A [max. 25 Amps]

6 Amps

Output on, automatic delay time before turning

the output on

[Disabled], [Set delay, step: 1 sec]

0 sec.

Output off, automatic delay time on battery

after which output is turned off

[Disabled], [Set delay, step: 1 sec]

Disabled

User preferences:
Operation priority while rectifier input break

[On battery], [On bypass]

On battery

Site wiring fault w/ wrong Neutral connection [Enabled], [Disabled]

Enabled

Power Strategy

[Standard], [High Efficiency]

Standard

Parallel settings:
Parallel unit number

[Single unit], [Unit #1], [Unit #2], [Unit #3],

[Unit #4]

Single unit

Parallel operation mode

[Redundant mode], [Capacity mode]

Redundant mode

Synchronization

[Enabled], [Disabled]

Enabled

Start auto calibration
Parallel XCP

[System], [Unit]

System

Minimum units to support load

[0], [1], [2], [3], [4]

2

Table 5 User setting in the LCD menu screen.